3.5.3 System Application - Zone System with Pumps (Primary/Secondary Piping)
Return filter
Not to exceed 4 pipe Dia or Max. 12"
System application drawings are intended to explain the system piping concept only.
Note
Install a filter in the system return to remove foreign objects from the system. Foreign objects inside the system may result in
abnormal system operation.
Refer to "3.3 Filling the System" on page 27 for make-up water connections and refer to the requirements of your local codes
to ensure compliance.
Use a pump with an integral check valve or install a check valve at the pump outlet.
Refer to "3.6.3 Wiring Diagram - Zone Pump System" on page 35 for wiring connections.
Additional Zone
Air Separator
Boiler Pump
Zone #2
Zone #1
Backflow preventer
Pressure reducing valve
Expansion Tank
Make-up Water
Installing the System Piping