* BGD36 HORIZONTAL VENT SECTIONS: A minimum of 1" (25mm) at the bottom and sides and 2" (51mm)
at the top of the vent pipe on all horizontal runs to combustibles is required. Use fi restop spacer W010-1774
(supplied).
* BGD36 VERTICAL VENT SECTIONS: A minimum of 1" (25mm) all around the vent pipe on all vertical runs
to combustibles is required except for clearances in appliance enclosures. See "MINIMUM ENCLOSURE
CLEARANCES" section. Use fi restop spacer W500-0096 (not supplied).
6.2.1 MINIMUM FRAMING DIMENSIONS
FOR TOP EXIT APPLICATIONS: DO NOT BUILD INTO THIS AREA. IT MUST BE LEFT CLEAR TO
PROVIDE ADEQUATE CLEARANCE FOR THE VENT. IN THIS 14" (356MM) WIDE AREA CENTRED
ALONG THE FRONT OF THE APPLIANCE, NO COMBUSTIBLES ARE ALLOWED.
14 1/2"
368mm
Combustion protrusions such as mantels and shelves may occur at or after a minimum distance of 2" (51mm)
away from the side of the appliance. Thereafter, the depth of any protrusions must be equal to or less than the
distance from the side of the appliance up to a depth of 6" (152mm), after which no greater clearance than 6"
(152mm) is required. This can be considered a side wall with no length boundary.
WARNING
!
14"
356mm
3 1/2"
1 1/2"
89mm
38mm
35 3/4"
908mm
34 3/4"
882mm
OUTSIDE
CHASE
37 3/4" 959mm
14 1/2"
368mm
37 3/4" 959mm
PROTRUSION
37
EN
14 1/2"
368mm
INSIDE
CHASE
2" 51mm
4" 102mm
2" 51mm
SIDE
4" 102mm
WALL
6" 152mm