Clearance to combustible walls
To find out whether the wall by which the stove is to be placed is combustible or not,
please contact your architect or the local building authorities.
If the floor is combustible, the stove must be placed on a non-combustible plate such
as steel, glass or stone. See pages 9 and 16 for additional information concerning floor
protection.
It may be possible to reduce clearances to combustible walls using the methods
detailed in NFPA 211. Seek guidance and permission in your locality as permits or
inspections may be required.
RAIS A/S
Clearances may only be reduced by means approved by regulatory authority
Industrivej 20, DK-9900 Frederikshavn, Denmark
Minimum Rear vent Clearance
(*
838040590 High socket complete
Room Heater
A: Side Wall to Unit
B: Back Wall to Unit
C: Corner Wall to Unit
D: Ceiling Height
E: Front Wall / Furnishing 36"/915mm
F: Back Wall to Pipe
G: Side Wall to Pipe
H Corner Wall to Pipe
Back wall
Back wall
G
G
A
A
14
User Manual Q-Tee II USA
User Manual Q-Tee II USA
RAIS A/S
Industrivej 20, DK-9900 Frederikshavn, Denmark
With Pedestal With Pedestal* No Pedestal
14"/356mm
Date of manufacture
Date of manufacture
12"/ 305mm
Date of fabrication
11"/280mm
Date of fabrication
45"/1143mm
15"/381mm
22,5"/572mm 22,5"/572mm 23,5"/597mm
20"/508mm
)
Rear vent
For Use With Solid Wood Fuel On
14"/356mm
Month
12"/305mm
N/A
Mois
45"/1143mm
36"/915mm
N/A
N/A
Adjacent wall
C
C
H
For Use With Solid Woo
15"/381mm
Month
15"/381mm
13"/331mm
Mois
45"/1143mm
36"/915mm
18"/458mm
22"/559mm
Adjacent wall
H
Teste
UL 1
ULC
Y
A