US English
When installed WITH optional base
The floor protection plate must lie under the stove and extend 16" (11cm) (18" (45cm)
in Canada) in front of the stove door, 8" (20cm) beyond the sides of the fuel-loading
door, and under the pipe and 2" (5cm) beyond each side for back venting. In Canada,
an 8" (20cm) floor protection is required beyond the sides of the stove and in the back
of the stove (0" in the back for the US). The floor protection needed on the floor when
used WITH the optional pedestal base, RAIS part number xxx, is not required to have
thermal protection (R=0).
Make sure that the floor and the sub-floor of the room in which the stove is installed is
designed to carry the extra weight of the stove. The floor protector plate must be made
of a non-combustible material.
When deciding where to install your stove, the heat distribution to other rooms should
be taken into consideration. Put the stove at a safe distance from combustible materi-
als; see the references at the name tag of the stove.