2.1 Water connections

Make the water connections to the appliance according to the indications shown both next to each fi tting and in Figure 2 of this booklet.
The connections must be made in such a way that the pipes are not under stress. The safety valve must be fi tted in the central heating circuit,
as close as possible to the boiler, without there being any obstructions or on-off devices between the boiler and the valve.
The appliance is not supplied with an expansion vessel, and therefore such device must be connected by the installer. Please note that in this
regard, the pressure in the system, when cold, must be between 0.5 and 1 bar.
2.2 Connecting the burner
Oil or gas jet burners for pressurised furnaces can be used if their operating characteristics are suitable for the dimensions of the boiler's
furnace and its over-pressure value. The burner must be chosen following the instructions provided by the manufacturer, according to the
fi eld of operation, fuel consumption and pressure, as well as the length of the combustion chamber.
Fit the burner following the instructions provided by the manufacturer of the device.

2.3 Electrical connections

The boiler should be connected to a single-phase, 230 Volt-50 Hz electrical line, using a permanent connection, installing a double
pole switch with contact openings of at least 3mm, and suitable fuses. Connect the burner and the room thermostat (if featured) as
shown in the wiring diagram in Chap. 4.
The electrical safety of the appliance is ensured only when the appliance is correctly connected to an effective earth system, as pre-
scribed by the safety standards in force. Have professionally qualifi ed personnel check the effi ciency and the rating of the earth system. The
manufacturer is not liable for any damage caused by the appliance not being correctly earthed. In addition, make sure that the electrical system
is adequately rated for the maximum power absorbed by the appliance, indicated on the rating plate, and in particular that the cross-section
of the wires is suitable for the power absorbed by the appliance.
2.4 Flue connections
The boiler should be connected to a suitable fl ue, manufactured in compliance with the standards in force. The pipe between boiler and the fl ue
must be made from material suitable for this purpose, that is, resistant to both high temperatures and corrosion. The joints should be carefully
sealed and the entire length of the pipe between the boiler and the fl ue should be thermally insulated, to avoid the formation of condensate.
2.5 Assembling the boiler
The boiler may be supplied:
1. As a set of elements, in 4 separate boxes, containing the Casing, Control panel, Elements, and accessories for assembling the elements.
Follow the instructions enclosed with the set of elements to assemble the boiler body. Follow the instructions below to assemble the casing
and control panel.
2. With the body already assembled, in 3 separate boxes containing the Casing, Control panel and Boiler body.
Follow the instructions below to assemble the casing and the control panel.
1
2
1
2
A
B
A If the boiler body
B Fit the rear panel 1 on
is supplied already
the studs 2 and loosely
assembled and is
tighten the bolts.
delivered from the
factory on a pallet,
remove the bolts 1
that fasten it to the
pallet and position it
for fi nal installation.
Then assemble the
various panels.
4
1
F. a. DX + SX +
7 elem.
C. a.
F. a. DX + SX +
8 elem.
C. a.
F. a. DX + SX +
9 elem.
2
C. a.
F. a. DX + SX +
10 elem.
C. a.
F. a. DX + SX +
11 elem.
C. a.
2
F. a. DX + SX +
12 elem.
C. a.
F. a. DX + SX +
13 elem.
C. a.
F. a. DX + SX +
14 elem.
C. a.
C
C Prepare the right and left sides, choosing the quantity of side panels according to
the dimensions of the boiler (see table).
F. 3 + C. 3
F. 1 + C. 1
F. 1 + C. 1
F. 2 + C. 2
F. 1 + C. 1
F. 2 + C. 2
F. 2 + C. 2
F. 2 + C. 2
F. 3 + C. 3
F. 3 + C. 3
F. 3 + C. 3
F. 1 + C. 1
F. 2 + C. 2
F. 2 + C. 2
F. 2 + C. 2
7 elem.
9÷12 elem.
13÷14 elem.
GN4 N
Side panels
F. a. DX = 330 mm (cod. 3703812/0)
F. a. SX = 330 mm (cod. 3703813/0)
F. 1 = 406 mm (cod. 3703814/0)
F. 2 = 536 mm (cod. 3703815/0)
F. 3 = 666 mm (cod. 3703816/0)
Cover
C. a. = 273 mm (cod. 3703822/0)
C. 1 = 406 mm (cod. 3703819/0)
C. 2 = 536 mm (cod. 3703820/0)
C. 3 = 666 mm (cod. 3703821/0)
F. 2 + C. 2
F. 2 + C. 2

Publicité

Table des Matières
loading

Table des Matières