Opposed configurations
120
180
450
900
fig. 16 - Opposed configurations
Table. 3 - Opposed configurations
Heating capacity
max.
Model
Model
kW
Module 1
Module 2
150
80
80
191
125
80
232
125
125
300
160
160
382
250
160
464
250
250
375
160
160
416
160
160
457
250
160
498
250
160
539
250
250
580
250
250
600
160
160
682
250
160
764
250
250
846
250
250
928
250
250
1003
250
250
1044
250
250
1078
250
250
1160
250
250
A
1
B
fig. 17 - Examples of opposed configurations
1
Model ENERGY TOP B 160 - 250
2
Model ENERGY TOP B 80 - 125
4
Safety devices and separator module
74
EN
A
Combinations
Model
Model
Model
Module 3
Module 4
Module 5
/
/
/
200
/
/
/
200
/
/
/
200
/
/
/
200
/
/
/
200
/
/
/
200
80
/
/
200
125
/
/
200
80
/
/
200
125
/
/
300
80
/
/
300
125
/
/
300
160
160
/
300
160
160
/
300
160
160
/
300
250
160
/
300
250
250
/
300
250
250
80
300
250
250
125
300
250
250
160
300
250
250
250
300
4
4
2
cod. 35401H060 - Rev. 01 - 02/2018
3.2 Place of installation
The generator can be installed directly outside or in a suitable room with ventilation open-
ings to the outside as prescribed by the current regulations. If there are several burners
or extraction units that can work together in the same room, the ventilation openings
must be sized for simultaneous operation of all the units. The place of installation must
be free of flammable objects or materials, corrosive gases, volatile substances or dusts.
For positioning, leave enough space around the modules for normal maintenance oper-
ations. Make sure the front door opens without hindrance.
B
The air necessary for combustion enters through special openings in the bot-
tom and top part of the unit. Make sure these air passages are not obstructed
in any way.
Ø;
A
3.3 Gas and water connections
500
Plumbing connections
500
Make the relevant connections according to the instructions given below. Make the gen-
500
erator connection in such a way that its internal pipes are free of stress. For proper op-
1000
eration and long life of the generator, the plumbing system must be of suitable size and
1000
complete with all the accessories that guarantee regular operation and running.
1000
In particular, provide for all the protection and safety devices prescribed by current reg-
1500
ulations for the complete modular generator. They must be installed on the hot water cir-
cuit delivery piping, immediately downstream of the last module, within a distance of 0.5
1500
m, with no shut-off devices in between. A "Safety Device and Circuit Breaker module"
1500
equipped with internal hydraulic circuit breaker and safety units with ISPESL certification
1500
is available by request. Refer to the price-list or contact our sales network. The unit is not
supplied with an expansion tank; its connection must therefore be made by the Installer.
1500
B
A filter must also be installed on the system return piping to prevent impurities
1500
or sludge from the system clogging and damaging the heat generators.
2000
The filter must necessarily be installed when replacing generators in existing
2000
systems. The manufacturer declines any liability for damage caused to the gen-
2000
erator by failure to install or inadequate installation of this filter.
2000
2000
2500
2500
3000
3000
ENERGY TOP B
fig. 18 - Air inlet