Technical Data - Phoenix Contact PSR-SCP-24DC/RSM4/4X1 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

6. Technical data

Connection method
Pluggable screw terminal block
Order No.
Pluggable spring-cage terminal block Order No.
Input data
Nominal input voltage U
N
Permissible range
Typ. current consumption at U
N
Voltage at input/start and feedback circuit
Typ. response time (K1, K2) at U
N
Typ. release time (K1, K2) at U
N
Limit frequency
IN1, IN2
Permissible encoder signals
Recovery time
Output data
Contact type
Contact material
1)
Max. switching voltage
Min. switching voltage
Limiting continuous current
2
2
2
2
2
I
= I
+ I
+ I
+ I
TH
1
2
3
4
Max. inrush current
Min. switching current
Max. power rating
24 V DC
48 V DC
110 V DC
220 V DC
Min. switching capacity
Mechanical life
Switching capacity
Short circuit protection of output circuits, external
1)
When the gold layer is intact.
When the gold layer is destroyed, the values in
brackets are valid.
18
PSR-RSM4
PSR-SCP-24DC/RSM4/4X1
PSR-SPP-24DC/RSM4/4X1
24 V DC
0.85 ... 1.1 x U
N
100 mA
24 V DC
15 ms
12 ms
2 kHz
RJ45
400 kHz
Low
0.0 ... 0.8 V DC
High
2.0 ... 26.4 V DC
1 s, approximately
4 enabling current paths
Silver nickel 10 (AgNi10),
gold-flashed (5 μm Au)
60 V AC/DC (250 V AC/DC)
100 mV AC/DC
5 A
2
42.25 A
6 A
1 mA
Ohmic load
τ
= 0 ms
67 W
36 W
43 W
68 W
1 mW
6
Approx. 50 x 10
cycles
Cycles
DC 13
360/h:
24 V:
2 A
230 V:
6 A gl (DIN EN 60947-5-1)
Technical data
General data
2981538
Permissible ambient temperature
2981541
Rated operating mode
Degree of protection in acc. with VDE 0470 part 1
- Connection terminal blocks
Mounting position
Air and creepage distances between the power
circuits
Rated voltage
Impulse voltage withstand level
Pollution degree
Surge voltage category
Dimensions (W / H / D)
Conductor cross section
Material of housing
2)
Safe isolation, increased insulation and 6 kV between input circuit and output contact current paths.
Response time
The total response time is calculated from:
- The response time of speed monitoring
- The release time of the output relay (12 ms) and
- The shutdown times of the external switching elements
There is a linear decrease in the response time of speed monitoring when the speed to be
monitored increases:
It is approx. 500 ms at 6 Hz and 30 ms at 100 Hz.
The following applies:
• Downtime monitoring to zero is not possible.
• The minimum adjustable frequency for downtime is 1.3 Hz.
• When parameterizing the downtime and all the maximum speed to be monitored (Vmax),
AC 15
ensure that the ratio of the frequency of Vmax and the downtime is > 6. If the ratio is < 6,
the single-channel property of the sensors is not detected.
This measure is necessary to ensure the operational reliability.
3 A
Note:
When operating relay assemblies, the operator must see that the requirements pertaining to emitted
interference for electrical and electronic operating equipment (EN 61000-6-4) are observed on the
contact side, and perform any necessary measures.
PSR-RSM4
-20°C ... +55°C
100% operating factor
- Housing
IP40
IP20
- Point of installation
Minimum IP54
Any
In acc. with EN 60664/VDE 0110
2)
Basic insulation
250 V
2)
4 kV
2
III
PSR-SCP-...
(45 / 114.5 / 99) mm
PSR-SPP-...
(45 / 114.5 / 112) mm
2
screw connection
0.2 - 2.5 mm
(AWG 24-12)
2
spring-cage connection
0.2 - 1.5 mm
(AWG 24-16)
Polyamide PA non-reinforced
19

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Psr-spp-24dc/rsm4/4x129815382981541

Table des Matières