General information
Content
This appendix includes BACnet MS/TP specific information linked to BTU meter CALEC
main operating manual.
General information to BACnet: www.bacnet.org
Ordering process
BACnet MS/TP module also available as spare part: Parts No. 80628.
®
CALEC
ST: Overview of supported functions
Function
Aquametro vendor ID
Data protocol
BACnet device profile
MAC address
Baud rate
Device instance number
BACnet connection type
2 2
Parameter
431
BACnet MS/TP
B-ASC
0...127 master
and slave
0...254 slave
9600, 19200, 38400,
76800
®
ST. General information of CALEC
Description
Factory setting: the lower 2
digits of the device serial no.
master/slave changeover:
Changeable via CALEC
®
ST
operating menu.
Factory setting: master
Automatically adjustment
5 lower digits of the BTU
meter serial no.
RS 485
®
ST are in the
More information
See: Mode master/slave
See: BACnet baud rate
See: Device object instance number
(DIN)