Troubleshooting Tips - Friedrich Kühl KCS08 Manuel D'installation Et D'utilisation

Masquer les pouces Voir aussi pour Kühl KCS08:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Troubleshooting Tips

COMPLAINT
CAUSE
The unit is turned to the off position, or the
thermostat is satisfied.
The LCDI power cord is unplugged.
Unit does not operate.
The LCDI power cord has tripped (Reset
button has popped out).
The circuit breaker has tripped or the
supply circuit fuse has blown.
There has been a local power failure.
Other appliances are being used on the
same circuit.
An extension cord is being used.
Unit Trips Circuit Breaker or
Blows Fuses.
The circuit breaker or time-delay fuse is
not of the proper rating.
The LCDI power cord can trip (Reset
button pops out) due to disturbances on
your power supply line.
LCDI Power Cord Trips
Electrical overload, overheating, or cord
(Reset Button Pops Out).
pinching can trip (Reset button pops out)
the LCDI power cord.
NOTE:
A damaged power supply cord must be replaced with a new power supply cord obtained from the
product manufacturer and must not be repaired.
The return/ discharge air grille is blocked.
Windows or doors to the outside are open.
The temperature is not set at a cool
enough/ warm enough setting.
Unit Does Not Cool/ Heat Room
The filter is dirty or obstructed.
Sufficiently, or Cycles On And Off
Too Frequently.
The indoor coil or outdoor coil is dirty or
obstructed.
There is excessive heat or moisture
(cooking, showers, etc.) in the room.
The temperature of the room you are
trying to cool is extremely hot.
46
SOLUTION
Turn the unit to the on position and raise or lower
temperature setting (as appropriate) to call for
operation.
Plug into a properly grounded 3 prong receptacle.
See "Electrical Rating Tables" on Page 6 for the
proper receptacle type for your unit.
Press and release RESET (Listen for click. Reset
button latches and remains in.) to resume operation.
Reset the circuit breaker, or replace the fuse as
applicable. If the problem continues, contact a
licensed electrician.
The unit will resume normal operation once power
has been restored.
The unit requires a dedicated outlet circuit, not shared
with other appliances.
Do NOT use an extension cord with this or any other
air conditioner.
Replace with a circuit breaker or time-delay fuse of
the proper rating. See "Electrical Rating Tables" on
Page 6 for the proper circuit breaker/ fuse rating for
your unit. If the problem continues, contact a licensed
electrician.
Press and release RESET (Listen for click. Reset
button latches and remains in.) to resume normal
operation.
Once the problem has been determined and
corrected, press and release RESET (Listen for
click. Reset button latches and remains in.) to
resume normal operation.
Ensure that the return and/ or discharge air paths are
not blocked by curtains, blinds, furniture, etc.
Ensure that all windows and doors are closed.
Adjust the Temperature control to a cooler or warmer
setting as necessary.
Clean the filter, (see Routine Maintenance), or
remove obstruction.
Clean the coils, (see Routine Maintenance), or
remove obstruction.
Be sure to use exhaust vent fans while cooking or
bathing and, if possible, try not to use heat producing
appliances during the hottest part of the day.
Allow additional time for the air conditioner to cool off
a very hot room.
Troubleshooting Tips continued
COMPLAINT
CAUSE
The outside temperature is below 60 °F
(16 °C).
The digital control is set to fan cycling mode.
Unit Does Not Cool/ Heat Room
Sufficiently, or Cycles On And Off
Too Frequently (continued).
The air conditioner has insufficient cooling
capacity to match the heat gain of the room.
The air conditioner has insufficient heating
capacity to match the heat loss of the room.
This may be due to an excessive heat load
in the room.
It may also be due to an improperly sized unit.
This may be normal for higher efficiency
Unit Runs Too Much.
(EER) air conditioners.
You may notice that the discharge air
temperature of your new air conditioner
may not seem as cold as you may be
accustomed to from older units. This
does not; however, indicate a reduction
in the cooling capacity of the unit.
SOLUTION
Do not try to operate your air conditioner in the
cooling mode when the outside temperature is below
60 °F (16 °C). The unit will not cool properly, and the
unit may be damaged.
Since the fan does not circulate the room air
continuously at this setting, the room air does not
mix as well and hot (or cold) spots may result. Using
the continuous fan setting is recommended to obtain
optimum comfort levels.
Check the cooling capacity of your unit to ensure it
is properly sized for the room in which it is installed.
Room air conditioners are not designed to cool
multiple rooms.
Check the heating capacity of your unit. Air conditioners
are sized to meet the cooling load, and heater size
is then selected to meet the heating load. In extreme
northern climates, room air conditioners may not be able
to be used as a primary source of heat.
If there are heat producing appliances in use in the
room, or if the room is heavily occupied, the unit will
need to run longer to remove the additional heat.
Be sure to use exhaust vent fans while cooking or
bathing and, if possible, try not to use heat producing
appliances during the hottest part of the day.
The use of higher efficiency components in your new
air conditioner may result in the unit running longer
than you feel it should. This may be more apparent, if
it replaced an older, less efficient, model. The actual
energy usage, however, will be significantly less
when compared to older models.
The energy efficiency ratio (EER) and cooling
capacity rating (Btu/ h) listed on the unit's rating
plate are both agency certified.
47

Publicité

Chapitres

Table des Matières
loading

Table des Matières