Overloaded, check load situation and ramps.
Short circuit or earth fault, check load and wiring.
Asymetric load current, check load and wiring.
Phase current too high, check load and wiring.
Message from phase monitoring, check load and wiring.
DC link voltage too high, check deceleration ramps and connected brake resistor.
DC link voltage low, check mains voltage.
Power failure, check mains voltage and circuit.
Phase failure, check mains fuses and circuit.
Mains voltage UDC too high on switch-on, check voltage.
Mains voltage BC too high on switch-on, check voltage.
Mains voltage MC too high on switch-on, check voltage.
Electronic voltage too low, check control terminals.
Electronic voltage too high, check wiring of control terminals.
Output frequency too high, check control signals and settings.
Max. frequency achieved by control, check deceleration ramps and connected
brake resistor
Monitoring function of Release Inputs A/ B
Diagnosis error; at least one the secure disable lines A and B is faulty.
Check the devices on the secure disable lines, Check wiring and EMC.
The self-diagnosis software has detected an internal error.
The parameter
Error Environment 1
Contact the service of BONFIGLIOLI.
Error message of the 5-second-monitoring. The secure disable lines are not
switched at the same time; the admissible time of 5 seconds was exceeded.
Check the control of the secure disable lines.
Earth fault on output, check load and wiring.
Control connection
Reference signal on multifunctional input 1 faulty, check signal.
Overcurrent on multifunctional input 1 faulty, check signal.
49
Output current
DC link voltage
Electronic voltage
Output frequency
262 describes the cause of error.