Technical Data; Scope Of Delivery; Accessories - Wilo FLA Compact Notice De Montage Et De Mise En Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

English
5.2

Technical data

Max. volume flow
Max. delivery head
Speed
Mains voltage
Rated current
Frequency
Electrical connection
Insulation class
Protection class
Power consumption P
1
Power consumption P
2
Permitted ambient temperature
Approved fluids
Admissible fluid temperature
Maximum permitted operating pressure
Max. permissible inlet pressure
Nominal diameters
Connection replenishment valve on the
break tank FLA Compact-1
Connection replenishment valve on the
break tank FLA Compact-2
Pressure pipe connection FLA Compact-1
Pressure pipe connection FLA Compact-2
Break tank
Material
Ambient temperature
Float switch (protection against low water
level; overflow signal transmitter)
Max. switching voltage
Max. switching current
Max. switching capacity
Material
Protection class
Further data...
Diaphragm pressure vessel

5.3 Scope of delivery

• Fire-extinguishing system Wilo-FLA Compact
(system with switchgear, pump(s) and break tank)
• Installation and operating instructions for the fire-
extinguishing system Wilo-FLA Compact
• Installation and operating instructions for the
pumps
• Installation and operating instructions for the
control device
• Factory acceptance test certificate
(in accordance with EN10204 3.1.B)
• Installation plan (if applicable)
• Electrical circuit diagram (if applicable)
• Installation and operating instructions for the
signal transmitter (if applicable)
• Spare parts list (if applicable)
• Additional documentation for special versions
(if applicable)
26
See catalogue/data sheet
See catalogue/data sheet
2800 – 2900 rpm
3~ 400 V ±10 % V (L1, L2, L3, PE)
See rating plate
50 Hz
F
IP54
See rating plate of pump/motor
See rating plate of pump/motor
5 °C to 40 °C
Pure water without settling sediments
3 °C to 50 °C
On the pressure side 10/16 bar (DS8 to PN 10; DS16 to PN 16)
See inlet pressure fresh water
G2 (Helix V 16.. / Helix V 22..).
2 x G 2 (Helix V 1612 / Helix V 22..).
R 1½ (Helix V 1604 - 1611)
R 2 (Helix V 1612 / Helix V 22..)
R 2½ (Helix V 1604 - 1611)
R 3 (Helix V 1612 / Helix V 22..).
Polyethylene (PE-HWU) black
Filled +5 °C to +40 °C
Empty -20 °C to +60 °C
48 V
0.5 A
3 W / 3 VA
PVC
IP67
8 l (see rating plate diaphragm expansion tank)

5.4 Accessories

• Flexible connection pipes
• Compensators
• Threaded flange
• Diaphragm expansion tank
• Flushing apparatus kit in accordance with
Accessories must be ordered separately as
required. The accessories from the Wilo range
include the following:
DIN 1988-600
WILO SE 07/2019

Publicité

Table des Matières
loading

Table des Matières