GMV DC Inverter VRF
air, pay attention to the spaces where the refrigerant may residue, for example, the basement.

4.5 Electric Wiring

4.5.1 Wiring precautions

 Wiring should conform to national rules. All the parts, materials, electric work should be in
accordance with local codes.
 Rated voltage and exclusive power supply should be used.
 Power cord should be fixed soundly and reliable. Never forcibly pull the power cord.
 Wire size of power cord should be large enough. The damaged power cord and
connecting wire should be replaced by exclusive cable.
 All the electrical work should be performed by professional personnel as per local law,
regulation and this manual.
 Connect the unit to the special earthing device and make sure the unit is earthed soundly.
 Circuit breaker and circuit breaker is required to be set. Circuit breaker should have both
magnetic trip and thermal trip functions so as to protect the unit when short-circuit and
overload happens. D-type breaker is adviced to be used.
 Wiring diagram attatched on the unit is prevailed.
4.5.2 Wiring of power cord
Every unit should have corresponding short-circuit and overload protection. And also a
main switch is required to control power supply or disconnection. See Fig. 4.5.1.
Please refer to the following table for circuit breaker and circuit breaker for modular
outdoor units. 5-core cable is used and the wire size unit is mm
Model
Basic models
GMV-224WM/E-X
GMV-280WM/E1-X
GMV-280WM/E-X
GMV-335WM/E-X
GMV-400WM/E-X
GMV-450WM/E1-X
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Fig. 4.5.1
Circuit
Circuit breaker
breaker
capacity for
capacity
combined units
(A)
-
20
-
25
-
25
-
32
-
40
-
40
35
2
.
Wire size of
power supply
2
(mm
)
(A)
20
2.5
25
2.5
25
2.5
32
4.0
40
6.0
40
6.0
Wire size of combined
2
uni (mm
)
2.5×5
2.5×5
2.5×5
4.0×5
6.0×5
6.0×5