Gree GMV-680WM/E-X Manuel D'utilisateur page 54

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

GMV DC Inverter VRF
Debugging
——
code
LED1
progress
Display
Code
status
db
02_Allocate
db
addresses
db
db
03_Confirm the
quantity of
modules
db
db
04_Confirm the
quantity of IDUs
db
db
db
05_Detect
internal
communication
db
db
db
db
06_Detect
outdoor
components
db
db
07_Detect
indoor
components
db
db
08_Confirm
preheated
compressor
db
db
09_Refrigerant
judgments
before startup
db
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Description of each stage of debugging progress
Progress code
LED2
Display
code
Code
status
light
02
light
light
02
light
light
02
light
light
03
light
01~04
light
03
light
light
04
light
01~80
light
04
light
light
05
light
light
05
light
light
05
light
light
05
light
light
05
light
light
06
light
Error code
light
06
light
XXXX/Error
light
07
light
code
light
07
light
light
08
light
light
08
light
light
09
light
light
09
light
Status code
LED3
Display
status
Ad
blink
System is allocating addresses.
Master IDU is not set. Please set
master IDU. If it's not set in 1min,
L7
blink
system will set the master IDU
randomly.
Allocation is finished. Start next
OC
light
progress.
LED3 displays the quantity of modules.
blink
Confirm the number manually.
System has confirmed the quantity of
OC
light
modules. Start next progress.
LED3 displays the quantity of IDUs.
blink
Confirm the number manually.
System has confirmed the quantity of
OC
light
IDUs. Start next progress.
System detects "driven communication
C2
light
error between master unit and inverter
compressor".
System detects "driven communication
C3
light
error between master unit and inverter
fan".
IDU/ODU "high proportion of rated
CH
light
capacity".
IDU/ODU "low proportion of rated
CL
light
capacity".
Detection is finished. Start next
OC
light
progress.
System detects error in outdoor
light
components.
No error in outdoor components. Start
OC
light
next progress.
System detects error in indoor
components. XXXX is the project no. of
the faulted IDU. 3s later, relevant error
light
code is displayed. For example, IDU
no. 100 has d5 error, then LED3
displays like this: 01 (2s later) 00 (2s
later) d5, and repeat again.
No error in indoor components. Start
OC
light
next progress.
Preheat time for compressor is less
U0
light
than 8h.
Preheat time for compressor is 8h.
OC
light
Start next progress.
System refrigerant is not enough.
U4
light
System downtime equilibrium pressure
is lower than 0.3MPa.
System refrigerant is normal. Start next
OC
light
progress.
51
Meaning