Floor Ceiling Type Unit
5.4.4 Testing of Drain Piping
After piping work is finished, check if drainage flows smoothly.
(1).
As shown in the Figure, pour water into the drain pan from the right side to
(2).
check that water flows smoothly from the drain hose.
5.5 Electrical Wiring
5.5.1 Wiring Precautions
Before obtaining access to terminals, all supply circuits must be disconnected.
①.
The rated voltage of the unit is as shown as Table 3
②.
Before turning on, verify that the voltage is within the 185~264V range (for single phrase
③.
unit) or 342~457V range (for three-phrase unit).
Always use a special branch circuit and install a special receptacle to supply power to the
④.
air conditioner.
Fig. 24
Fig. 25
WARNING!
25