Debugging
——
code
LED1
progress
Display
Code
status
db
light
10_Status
judgments of
db
light
outdoor valves
before startup
db
light
11_Calculate
refrigerant
db
light
quantity
manually
db
light
12_Confirm
debugging
db
light
startup
——
——
13_
——
——
14_
db
light
db
light
db
light
15_Cooling
db
light
debugging
db
light
db
light
db
light
db
light
16_Heating
db
light
debugging
db
light
17_Debugging
01~04
light
finished
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Description of each stage of debugging progress
Progress code
Status code
LED2
LED3
Display
code
Code
status
10
light
ON
10
light
U6
10
light
OC
11
light
AE
12
light
AP
12
light
AE
——
——
——
——
——
——
15
light
AC
15
light
Error code
15
light
J0
15
light
U9
15
light
XXXX/U8
16
light
AH
16
light
Error code
16
light
J0
16
light
U9
16
light
XXXX/U8
OF
light
OF
52
GMV DC Inverter VRF
Meaning
Display
status
light
Outdoor valves are being turned on.
light
Outdoor valves are not fully turned on.
light
Outdoor valves are turned on normally.
Calculate the refrigerant quantity
manually and confirm the perfusion
light
status of refrigerant (the quantity of
refrigerant added into the system must
be recorded accurately).
blink
Ready for units to start debugging.
Manual calculation of refrigerant
light
quantity is set up.
——
no meaning.
——
no meaning.
Debugging is enabled in cooling mode
light
(debugging mode, auto-selected by
system).
Error occurs during debugging in
light
cooling mode.
Error of other modules occurs during
light
debugging in cooling mode.
Outdoor pipeline and valves are not
light
normal.
System detects error in indoor pipeline.
XXXX is the project no. of the faulted
IDU. 3s later, error code U8 is
light
displayed. For example, IDU no. 100
has U8 error, then LED3 displays like
this: 01 (2s later) 00 (2s later) U8, and
repeat again.
Debugging is enabled in heating mode
light
(debugging mode, auto-selected by
system).
Error occurs during debugging in
light
heating mode.
Error of other modules occurs during
light
debugging in heating mode.
Outdoor pipeline and valves are not
light
normal.
System detects error in indoor pipeline.
XXXX is the project no. of the faulted
IDU. 3s later, error code U8 is
light
displayed. For example, IDU no. 100
has U8 error, then LED3 displays like
this: 01 (2s later) 00 (2s later) U8, and
repeat again.
Debugging is finished. System is on
standby condition. LED1 displays
light
module address. LED2 and LED3
display "OF".