Precautions On Refrigerant Leakage - Gree GMV-680WM/E-X Manuel D'utilisateur

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

R (Quantity of added refrigerant in total) = 5+0=5kg
Modular combination of outdoor unit subjects to combinations that is currently available.
After confirming that there is no leakage from the system, when the compressor is not in
operation, charge additional R410A with specified amount to the unit through the filling opening
of the liquid pipe valve of the outdoor unit. If required additional refrigerant can not be quickly
filled for increase of pressure in the pipe, set the unit at cooling startup and then fill the
refrigerant from gas valve of outdoor unit. If ambient temperature is low, the unit can't be set to
cooling mode but heating mode.

4.4.3 Precautions on Refrigerant Leakage

(1)Personnel related to air conditioning engineering design and installation operators
must abide by the safety requirement for preventing refrigerant leakage specified in local laws
and regulations.
(2)The units adopt the R410A refrigerant, which is nonflammable and nontoxic. However,
the space for refrigerant leakage must be sufficient to ensure that the refrigerant concentration
does not exceed that specified in the safety requirement; otherwise, people involved can be
stifled by the refrigerant. For example the maximum allowed concentration level of refrigerant to
a humanly space for R410A according to the appropriate European Standard is limited to 0.44
3
kg/m
.
The maximum amount of refrigerant (kg) in the system = The volume of the room (m
maximum allowed concentration level of refrigerant (kg/m
Total amount of refrigerant (kg) in the system = Total additional charging amount (kg) +
Amount of refrigerant (kg) which is charged before leaving the factory (for the system
consisting of multiple modules in parallel, the accumulative charge quantity of modules before
leaving the factory is used)
Total amount of refrigerant (kg) in the system ≤The maximum amount of refrigerant (kg) in
the system
(3)When the total amount of refrigerant in the system is more than the maximum amount
of refrigerant, the cooling system should be designed again. In this case, the cooling system
can also be separated into several cooling systems with small capacity, or add corresponding
ventilation measures or alarming display.
① Flow direction of refrigerant leakage.
② Room for refrigerant leakage. Since the concentration of refrigerant is greater than that of
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
3
)
Fig. 4.4.3
34
GMV DC Inverter VRF
3
) ×The