installing flashing and storm collar

The following are generic installation instructions for installing the flashing around a chimney. Installation of all
types of factory-built chimney systems is to be in accordance with the chimney manufacturer's installation
instructions. Remove the nails from the shingles above and to the sides of the chimney. Place the flashing over
the chimney pipe and slide underneath the sides and upper edge
of the shingles. Ensure that the chimney pipe is properly
centered within the flashing, giving a 3/4" (19.1mm) margin all
around. Fasten to the roof on the top and sides. DO NOT NAIL
through the lower portion of the flashing. Make weather-tight by
sealing with caulking. Where possible, cover the sides and top
edges of the flashing with roofing material. Apply waterproof
caulking, provided with the flashing, around the chimney, 1"
(25.4mm) above the top of the flashing and push the storm collar
down into the caulking. Insert a rain cap onto the top of the last
chimney section.
4.6

air cooled chimney installation

WARNING
!
Do not block the outside air inlet opening on the exterior of the house. Doing so will result in fire or death.
This appliance has been tested for use with DuraVent,
DuraChimney II. The NZAC8KT air housing must be used in
conjunction with DuraVent 8DCA-AP starter collar to complete
the installation.
1. Install the starter collar using the gasket provided over the flue
and fasten to the top of the fireplace.
2. Slide the air housing onto the first section of the chimney and
secure the chimney to the starter collar.
3. Slide the air housing down the chimney section and secure
housing to the top of the fireplace.
4. Connect the outside air connection for the chimney.
note:
Air slots in the starter collar are to be completely
covered by the air housing
note:
Follow the chimney manufacturer's instructions
for installing the chimney
note:
Use 111KT outside air kit to connect to air
housing. Maximum length of 4" (101.5mm) liner
is 20' (6m). If greater length is required then
increase the liner diameter to 6" (154.4mm).
note:
An air cooled chimney requires its own dedicated outside air supply with a minimum of 4" liner diameter. (Not
to be shared with appliance outside air).
RAIN CAP
CAULKING
STORM COLLAR
39.13
DURA CHIMNEY II SECTION
AIR HOUSING
installation
EN
WEATHER
SEALANT
FLASHING
4" (102mm) LINER
DURAVENT 8 DCA - AP
STARTER COLLAR
2