Festo AS-Interface ASI-EVA Manuel D'installation page 23

Le module as-interface pour distributeurs type asi-eva
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 39
Proceed as follows:
1. Connect the earth connection (M3) with low impe-
dance to the earth potential.
2. Connect the cable sockets as described in the separate
brief description.
3. Lay the AS-Interface cable free of tension.
4. Mount the cable socket and screw it tight.
Recommendation: For connecting the AS-Interface cable
use the Festo cable sockets ASI-SD-FK or ASI-SD-FK180.
In this way you will comply with protection class IP65.
1
AS-Interface bus:
Pin 1 = - (light blue)
Pin
2 = + (brown)
2
Additional power supply: *)
Pin 1 = 0 V *)
Pin 2 = + 24 V *)
*)
Connection only if the load voltage supply is configured accord-
ingly (see 3.7). Seal non-used connections with the blanking plug
type ASI-SD-FK-BL.
Caution
Functional damage.
Do not disconnect power supplies under load.
Festo ASI-EVA... 0105NH English