Pp 45 Rc Fault Messages; Technical Data - Maico PP 45 O Notice D'utilisation

Système de ventilation pushpull
Masquer les pouces Voir aussi pour PP 45 O:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

UK | 12 Display

11.3 PP 45 RC fault messages

Red
Fault
LED
Internal error in
control
Master-slave com-
munication
Internal sensor
defective (I2C)
External sensor not
reporting
No communication
with the EnOcean
module PP 45 EO
The faults are not acknowledged.
Acknowledgement takes place
automatically when the fault is remedied.
38
Display
Fault LED
in alternation:
lit up for extended
period and then
flashes briefly once
Fault LED
in alternation:
lit up for extended
period and then
flashes briefly twice
Fault LED
in alternation:
lit up for extended
period and then
flashes briefly three
times
Fault LED
in alternation:
lit up for extended
period and then
flashes briefly four
times
Fault LED
in alternation:
lit up for extended
period and then
flashes briefly five
times

12 Technical data

External diameter
Wall sleeve max. length 500 or 800 mm
Wall thickness min.
max.
Air filter outside
Air filter inside
Air volume/unit
Protection class / degree
of protection
Sound power L
wA7,
free outlet
Rated voltage/
power frequency
Volumetric flows for
ventilation levels 1, 2,
3, 4, 5
Power consumption
Permissible ducting
lengths with wired
connection
Radio components:
Frequency range (in acc.
with EN 300220-1)
"Wireless" operating
distances in the building
are dependant on the
building materials used:
DS 45 RC  PP 45 RC
PP 45 EO  PP 45 RC
PP 45 RC  PP 45 RC
● With PP 45 RC as
signal booster
DN 160
280 mm
490 / 790 mm
G3
G2
42 m³/h
IP 00 / 2
up to 28 dB(A), 15 m³/h
230 V
50/60 Hz
15 / 20 / 30 / 36 / 42 m³/h
1.2 / 1.7 / 2.1 / 2.8 / 3.5 W
From star point max.
25 m per ventilation unit
868.35 MHz
up to:
30 m
30 m
30 m
40 m

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Pp 45 kPp 45 rcRls 45 oRls 45 kDs 45 rc0095.0241

Table des Matières