3.4 Connect sensors (PNP inputs)
In order to connect the sensors, use cables of type
KM12−DUO−... or sockets of type SEA−GS−7, SEA−M12−5GS−
PG7, SEA−GS−11−DUO or SEA−5GS−11−DUO. Fasten the plug
with the aid of the union nuts.
Seal unused sensor connections with protective caps of
type ISK−M 12. Only in this way can you comply with
protection class IP65.
Please note
The inputs are based on IEC1131−2 type 02.
The inputs are resistant to short circuits. In the event
of a short circuit, the slave will be switched off. The
AS−Interface master regards this slave as missing.
When the short circuit has been eliminated, the slave
indicates immediately that it can function again.
1
Pin assignment of the sensor
connection:
1: 24 V
2: Input In 2
3: 0 V
4: Input In−1