Type
Load voltage connection (only when
configured by DIL−switch)
Rated value (protected against
incorrect polarity)
Residual ripple
Max. current consumption
(sum current, at 24 V)
Outputs (valve connection)
Voltage range
Max. current consumption
Without additional supply
With additional supply
Digital inputs
Max. current consumption
per input
sum current (all inputs)
Input current high/low
Logic level
Reference potential
Response delay
26
ASI−EVA ...
21.6 V ... 26.4 V DC
(24 V DC ±10%)
4 Vpp
Type ..−2E1A−.. Type ..−2E2A−..
0.5 A
0.5 A
(0.25 A per output)
Watchdog function active
after 50 ms (see 3.5)
Approx. 1.4 V under load volt
age or AS−Interface voltage
2 * 1 W coil
0.5 A (0.25 A per output)
2 inputs based on standard
IEC 1131−2 type 2, 24 V DC,
PNP, Status display LED
Without
With
additional
additional
supply
supply
100 mA
200 mA
100 mA
200 mA
6 mA / 2 mA at 5V
(2−wire sensor)
ON: 11 V ...30 V
OFF: − 30 V ... 5 V
0 V
Typ. 3 ms (at 24 V)
Festo ASI−EVA−...−2E..A−Z 0401b English