TYPICAL VENT INSTALLATION
EN
THE FIRST 2 FEET OF OUTER 7" (178MM) DIAMETER VENT PIPE FROM THE APPLIANCE MUST BE
WRAPPED IN THE 1" (25MM) THICK INSULATION SLEEVE (SUPPLIED). MAKE SURE THE INSULATION
IS PULLED DOWN TIGHT TO THE APPLIANCE WHEN INSTALLED. THERE AFTER, A 2" (51MM)
CLEARANCE ALL AROUND THEVENT PIPE FROM COMBUSTIBLE MATERIALS ON ALL HORIZONTAL
10" (254mm)
MINIMUM
46"
(1168mm)
When venting, the horizontal run must be kept to a maximum of 20 feet (6m). If a 20 foot (6m) horizontal run
is required, the appliance must have a minimum vertical rise immediately off the appliance of 57" (1448mm).
When terminating vertically, the vertical rise is a minimum 3 feet (1m) and a maximum 40 feet (12m) above the
appliance.
W415-1410 / 11.20.14
VENT SECTIONS IS REQUIRED.
24" (610mm)
MAXIMUM
56"
(1422mm)
PLUS RISE
WARNING
!
* FIRST TWO
FEET
REQUIRES
INSULATION
SLEEVE
46"
(1168mm)
16" (406mm)
MINIMUM
3 FEET (1m)
MINIMUM
40 FEET (12m)
MAXIMUM
45.6