Installation
2.5.3
FLOOR PROTECTION
In the event of heat sensitive or flammable flooring, this must
be protected (e.g., by means of steel sheets, marble slabs or
tiles). Whatever protection you choose, this must protrude at
least 300 mm at the front and 150 mm from the sides of the
stove and must withstand its weight and have a thickness of
at least 2 mm (see following fig.).
Floor
fig. 7 floor protections
2.5.4
MINIMUM CLEARANCE FOR POSITIONING THE
AIR INTAKE
The combustion air intake of the pellet boiler cannot be con-
nected to an air distribution system or to a wall air intake. The
described measures and requirements must be complied with
to ensure its correct and safe positioning. These distances
must be observed to prevent taking combustion air from an-
other source; for example, opening a window can suck out the
outside air, depriving the boiler of it.
The air intake must be located at least at:
1.5 m
1.5 m
Horizontally away
0.3 m
1.5 m
Away from
tab.2 min. clearances air intake positioning
Mod. ITACA-TROIA rev 01
Protection
Protection
min. 2 mm
beneath
Doors, windows, flue
gas exhausts, gaps,
etc.
Above
Flue gas outlet
translated from the original text
2.5.5
WATER MAINS CONNECTION
IT IS OBLIGATORY TO MOUNT AN ANTI-CONDEN-
SATION VALVE ON THE RETURN
The pellet boiler is equipped with a hydraulic heating circuit
complete with a circulator, safety valve, temperature probe
and pressure gauge. The heating circuit can be directly con-
nected to the system without adding other components.
Connection of the boiler to the water mains is carried out by
checking that the supplied fittings are compatible with those
of the mains. If this is not so, provide for proper connection
with suitable fittings, as indicated in fig.8.
1
2
3
Air intake with
non-lockable
grille
EN