4.4 Troubleshooting
Diagnostics
In case of operation faults or problems, the display flashes and the fault identification
code appears.
There are faults that cause permanent shutdown (marked with the letter "A"): to restore
operation just press the reset button (detail 6 -fig. 1) for 1 second or RESET on the op-
tional remote timer control if installed; if the boiler fails to start, it is necessary to firstly
eliminate the fault.
Faults marked with the letter "F" cause temporary shutdowns that are automatically reset
as soon as the value returns within the boiler's normal working range.
Table of faults
Table. 8 - List of faults
Fault code
Fault
A01
No burner ignition
Flame present signal
A02
with burner off
Overtemperature protec-
A03
tion activation
Fume extraction duct
A04
safety device activation
A05
Fan protection activated
No flame after ignition
A06
stage (6 times in 4 min-
utes)
F07
High fume temperature
F10
Delivery sensor 1 fault
F11
Return sensor fault
F12
DHW sensor fault
F13
Exchanger probe fault
F14
Delivery sensor 2 fault
F15
Fan fault
Supply voltage under
F34
170V
F35
Faulty mains frequency Electric mains trouble
Incorrect system water
F37
pressure
F39
External probe fault
A41
Sensor positioning
F42
Heating sensor fault
Possible cause
Cure
Check the regular gas flow to the
No gas
boiler and that the air has been elimi-
nated from the pipes
Check the wiring of the electrode and
Ignition/detection elec-
that it is correctly positioned and free
trode fault
of any deposits
Check the gas valve and replace it if
Faulty gas valve
necessary
Insufficient gas supply
Check the gas supply pressure
pressure
Check the trap and clean it if neces-
Trap blocked
sary
Electrode fault
Check the ionisation electrode wiring
Card fault
Check the card
Check the correct positioning and
Heating sensor damaged
operation of the heating sensor
No water circulation in the
Check the circulating pump
system
Air in the system
Vent the system
Fault F07 generated 3
See fault F07
times in the last 24 hours
Fault F15 generated for 1
See fault F15
hour (consecutive)
Ionisation electrode fault Check the position of the ionisation
electrode and replace it if necessary
Flame unstable
Check the burner
Gas valve Offset fault
Check the Offset adjustment at mini-
mum power
Remove the obstruction from the flue,
air/fume ducts obstructed
fume extraction ducts and air inlet and
terminals
Check the trap and clean it if neces-
Trap blocked
sary
The exchanger probe
detects an excessive tem-
Check the exchanger
perature for over 2 min-
utes
Sensor damaged
Wiring shorted
Check the wiring or replace the sensor
Wiring disconnected
Sensor damaged
Wiring shorted
Check the wiring or replace the sensor
Wiring disconnected
Sensor damaged
Wiring shorted
Check the wiring or replace the sensor
Wiring disconnected
Probe damaged
Check the wiring or replace the
Wiring shorted
exchanger probe
Wiring disconnected
Sensor damaged
Wiring shorted
Check the wiring or replace the sensor
Wiring disconnected
No 230V power supply
Check the 3-pin connector wiring
Tachometric signal inter-
Check the 5-pin connector wiring
rupted
Fan damaged
Check the fan
Electric mains trouble
Check the electrical system
Check the electrical system
Pressure too low
Fill the system
Water pressure switch
damaged or not con-
Check the sensor
nected
Probe damaged or wiring
Check the wiring or replace the sensor
shorted
Probe disconnected after
Reconnect the external probe or disa-
activating the sliding tem-
ble the sliding temperature
perature
Delivery sensor discon-
Check the correct positioning and
nected from the pipe
operation of the heating sensor
Sensor damaged
Replace the sensor
cod. 3540T631 - 01/2011 (Rev. 00)

5. TECHNICAL DATA AND CHARACTERISTICS

5
201
278
341
250
193
95
44
10
fig. 19 - General view
Table. 9 - Key of figures cap. 5
5 Sealed chamber
7 Gas inlet
10 System delivery
11 System return
14 Safety valve
16 Fan
19 Combustion chamber
22 Burner
29 Fume outlet manifold
32 Heating circulating pump
36 Automatic air vent
44 Gas valve
56 Expansion tank
72 Room thermostat (not supplied)
74 System filling cock
82 Ignition and detection electrode
95 Diverter valve
7
6
3
5
2
4
3
1
2
1
0
0
500
A = Boiler pressure losses - 1, 2 and 3 = Circulating pump speed
16
29
209
7
210
74
11
114 Water pressure switch
138 External probe (optional)
139 Remote timer control (optional)
155 Hot water tank temperature probe (optional)
161 Condensing heat exchanger
186 Return sensor
188 Ignition electrode
193 Trap
196 Condensate tray
201 Mixing chamber
209 Hot water tank delivery
210 Hot water tank return
250 System delivery filter
256 Modulating heating circulating pump signal
278 Double sensor (Safety + Heating)
341 Exchanger probe
1.000
1.500
Q [l/h]
EN
56
22
82
188
19
161
196
186
36
14
114
32
A
2.000
31

Publicité

Table des Matières
loading

Table des Matières