Service; Generator Maintenance - Mi-T-M GEN-6000-0MKD Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

GENERATOR MAINTENANCE

Keep all air vents clear.
Keep the generator clean. DO NOT spray with water.
Periodically check all fasteners and tighten, see the peri-
odic maintenance chart.
GFCI TEST RECORDS:
As with any other safety devices, the GFCIs supplied with
these generators must be checked every month to insure
that they are functioning properly. To test the GFCIs,
follow the instructions and then enter the date of the test
below.
1. With the generator running and the idle control switch
in the "START" position, push the "TEST" button. The
"RESET" button should pop out. This should result
in the power being off at both outlets of the duplex
receptacle. Verify this by plugging a test lamp into each
outlet.
WARNING: IF THE RESET BUTTON DOES NOT
POP OUT, DO NOT USE THE RECEPTACLE(S).
SEE
AUTHORIZED
SERVICE REPRESENTATIVE FOR SERVICE
IMMEDIATELY.
2. If the GFCI test correctly, restore power by FIRMLY
pushing the "RESET" button back in until you hear or
feel a distinctive "click". IF THE GFCI FAILS TO RESET
Year
Jan.
NOTE: Situations exist where a GFCI will not afford any protection against the hazards of electrical shock.
EXAMPLE: if a person touches two or more conductors from a damaged cord set and is not in direct contact
with the ground, he or she may receive a shock. Since there is no path to ground for a ground fault current to
flow through, the GFCI will not operate and serious injury may result.
The GFCI are merely an added safety feature. There are no substitutes for good safety precautions, correct
electrical practices and proper maintenance of cords, equipment and connections.
18

Service

MI-T-M
CUSTOMER
Feb.
March April
May
PROPERLY, DO NOT USE EITHER OUTLET OF THE
DUPLEX RECEPTACLE. Have the unit serviced by an
authorized Mi-T-M Customer Service Representative
immediately.
3. High vibration or severe mechanical shock loads may
cause the GFCIs to trip. IF EITHER GFCI TRIPS
BY ITSELF AT ANY TIME, reset it and perform test
procedures 1 and 2.
4. Repeat steps 1-3 for the second GFCI.
WARNING: ALTHOUGH THE ABOVE TEST
PROCEDURES
GFCI OPERATION ON AN UNGROUNDED OR
IMPROPERLY GROUNDED GENERATOR, THE
GENERATOR MUST STILL BE GROUNDED
PER
THE
LISTED ON PAGE 14 FOR THE GFCI TO
FUNCTION PROPERLY AND PROTECT THE
USER FROM ELECTRICAL FAULTS.
ENGINE:
The engine for this generator is governed to operate at
speeds close to 3600 RPM (60Hz) throughout the op-
erating load range. The no load speed (before a load is
applied) will be just a bit higher than the load speed and is
normally set to 3750 RPM.
June
July
Aug.
Sept.
WILL
INDICATE
GROUNDING
INSTRUCTIONS
Oct.
Nov.
Dec.
Operator's Manual
PROPER

Publicité

Table des Matières
loading

Table des Matières