V.5.a. Configuration menu with operator level access
Configuration
1. Selection of the setting type (see section V.5.b.1)
2. Modification of Night Cooling parameters (see section V.5.b.2)
3. Modification of CO2 setpoints (DIVA and QUATTRO only) (see section V.5.b.3)
V.6. Modification of function parameters (password 2222 required)

V.6.a. System control mode

[(1) section V.5.a]
Access: Configuration/Control function
The control type is pre-set in the CORRIGO to supply with external compensation It is also possible to switch to recovery
control mode.
(WARNING: if you wish to set the system according to an ambient temperature, select "Recover Ctrl" mode; any
other option will cause a system malfunction)

V.6.b. Ventilation parameters

[(2) section V.5.a]
Access: Configuration/Ventilation
The ventilation speed is pre-set to 85%. This value can be modified. It is also possible to modify the temperature for activation
of Night Cooling (daytime external temperature/day, etc.) and deactivate it.
V.6.c. CO2 setpoint for DIVA® QUATTRO® option
[(3) section V.5.a]
Access: Configuration/Ctrl CO2/COV
The CO2 setpoints are pre-set: LS = 800 ppm HS = 1000 ppm. When the CO2 level reaches 1000 ppm, the system will
increase the operating speed proportionally up to its maximum speed.
Adjustment function
Ventilation
Ctrl CO2/VO
Adjustment function
Mode:
Supply+ comp ext (1)
Ventilation on: YES (2)
Activation ext Setp.: 22°C (2)
T°ext night
high: 18°C (2)
Low: 10°C (2)
Temp internal mini: 18°C (2)
Speed:
85%
Ctl CO2/COV on:
If timer on ventilation on :
Fan speed 1/2: 800 ppm (3)
Fan speed 1/1: 1000 ppm (3)
Diff: 160 ppm
31