ENGLISH
V.3.b. Temperature control menu
Temperature control
(8) Setting the reference temperature (see section V.4.c)
V.3.c. Ventilation control menu
Air control
(5) Speed, pressure, flow rate setting (see section V.4.b)
frequency control SAF
(EH OR DIVA) %
Pressure control SAF
(LOBBY)
Pa
Flow control SAF
m3/h
(MAC2/QUATTRO)
frequency control EAF
(EH OR DIVA) %
Pressure control EAF
(LOBBY)
Pa
Flow control EAF
m3/h
(MAC2/QUATTRO)
Rif comp est
-5°C = 23°C (8)
0°C = 22°C (8)
5°C = 20°C (8)
Riferimento comp est
10°C = 18°C (8)
15°C = 18°C (8)
Manual frequency control SAF
Setp 1/1: 70% (5)
Setp 1/2: 50% (5)
Pressure control SAF
Setp 1/1: non utilisé
Setp 1/2: 150Pa (5)
Flow control SAF
Setp 1/1: 1500 m3/h (5)
Setp 1/2: 750 m3/h (5)
Manual frequency control EAF
Setp 1/1: 70% (5)
Setp 1/2: 50% (5)
Pressure control EAF
Setp 1/1: non utilisé
Setp 1/2: 150Pa (5)
Flow control EAF
Setp 1/1: 1500 m3/h (5)
Setp 1/2: 750 m3/h (5)
27