Minimum Clearance To Combustible Enclosures - Napoleon Fireplaces LHD62N Instructions D'installation Et D'opération

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

28
5.1

MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES

EN
THE FRONT OF THE APPLIANCE MUST BE FINISHED WITH ANY NON-COMBUSTIBLE MATERIALS
SUCH AS BRICK, MARBLE, GRANITE, ETC., AS LONG AS THESE MATERIALS NEVER OVERHANG
IMPORTANT: The LHD62 requires a minimum inside enclosure height of 96" (2.4m), measured from the
bottom of the appliance. For temperature requirements, this area must be left unobstructed. It is recommended
that the enclosure be ventilated at the top and bottom to circulate the hot air.
Before fi nishing in the appliance test the operation using the remote control, cycling it through all of its different
modes, see "OPERATION" section. Check pressure readings, see "PILOT BURNER ADJUSTMENT" section.
Once fi nished in, access to the control components can only be done through the inside of the appliance.
NOTE: JOINT COMPOUNDS AND TAPES
THAT ARE RESILIENT TO HEAT AND
CRACKING SHOULD BE USED WHEN
TAPING AND MUDDING SEAMS.
NON-COMBUSTIBLE
96"
(2438mm)
MINIMUM
ENCLOSURE
HEIGHT
TOP OF
APPLIANCE
OPENING
* Within the appliance enclosure a minimum 7" (178mm) clearance between the top of the vent pipe and
combustible materials is required. All other clearances within the enclosure, including where the vent pipe exits
the enclosure are subject to 2" (51mm) to the sides and bottom and 3" (76mm) to the top for horizontal and 1"
(25mm) for vertical.
** See venting section.
W415-1334 / 06.10.14
INTO THE APPLIANCE OPENING.
68"
(1727mm)
MINIMUM
28"
(711mm)
MINIMUM
WARNING
!
COMBUSTIBLE
7" (178mm)
MINIMUM
TOP OF
ENCLOSURE
COMBUSTIBLE
DRYWALL
STEEL
FRAME
9"
(228mm)
TO SIDEWALL
STUD