Napoleon Fireplaces LHD62N Instructions D'installation Et D'opération page 25

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

*HORIZONTAL VENT SECTIONS: A minimum clearance of 3" (76mm) to the top and 2" (51mm) to the
sides and bottom of the vent pipe on all horizontal runs to combustibles is required. Horizontal vent sections
within enclosures require a minimum clearance of 7" (178mm) at the top of the vent pipe, see "MINIMUM
CLEARANCE TO COMBUSTIBLE ENCLOSURES" section. Use fi restop assembly W010-2883 (supplied).
*VERTICAL VENT SECTIONS: A minimum of 1" (25mm) all around the vent pipe on all vertical runs
to combustibles is required except for clearances in appliance enclosures. Vertical vent sections within
enclosures require a minimum clearance of 2" (51mm) around the vent pipe. Use fi restop spacer W500-0681
(not supplied).
27"
686mm
2057mm
27"
686mm
9"
228mm
81"
81"
2057mm
83 5/16"
2117mm
3"
76mm
81"
2057mm
124 7/8"
3171mm
25
EN
W415-1334 / 06.10.14

Publicité

Chapitres

Table des Matières

Dépannage

loading

Ce manuel est également adapté pour:

Lhd62p

Table des Matières