5.2

Terminals

A1, A2
Supply voltage 230V 50/60Hz
B1, B2
Supply voltage 24 V AC/DC
X1, X2
Sensing device connection
13, 14
Safety contact safety relay 1
23, 24
Safety contact safety relay 2
31, 32
Safety contact alarm relay
Z1, Z2
Manual reset connection
S11, S12
Encoder inputs, reset
5.3

Models

Version
Housing
Supply voltage
Alarm relay
(switching contact
31, 32)
5.4

Operating modes

• The safety circuits can be output separately or switched in series (redundant switching contact
routing).
• Automatic reset (factory setting, S11, S12 unbridged):
The switching device automatically enables the safety circuits again if the sensing device is
actuated/fails or in the event of a power cut.
• Manual reset (S11, S12 bridge):
The switching device will only enable the safety circuits again once the reset button (terminals Z1, Z2)
has been actuated if the sensing device has actuated/failed or if there has been a power cut.
It is not possible to permanently activate or bypass the manual reset button.
SK 41-32
SK 41-32
Polyamide housing, 22.5mm wide, for mounting to 35 mm DIN carrier rail in
230V 50/60Hz and
230V 50/60Hz and
24 V AC/DC
24 V AC/DC
Activates after
Activates if the
approx. 1 s for
sensing device
approx. 3 s if the
is actuated or if
sensing device is
a sensing device
actuated or faulty.
fault is being
signalled.
SK 41-82
RLU
accordance with EN 60715.
115V 50/60Hz and
24V AC/DC
Activates after
approx. 1 s for
approx. 3 s if the
sensing device is
actuated or faulty.
SK 41-82
RLU
115V 50/60Hz and
24V AC/DC
Activates if the
sensing device
is actuated or if
a sensing device
fault is being
signalled.