3.1.2 Schematic of the T° sensors positioning in th e DFE unit
3.1.3 Label placed on the access panel of the DFE (

3.2 Power supply to the fans and the control devices

All the internal cables (fans, controls, sensors,) to the main switch are factory pre-wired. All the power supply wiring
that remains is the main power supply to the main switch (es).
Wiring specifications:
Unit type
Supply Voltage (1)
DFE 450
1 x 230V
DFE 600
1 x 230V
DFE 800
1 x 230V
DFE 1200
1 x 230V
(1) Grounding is compulsory
(2) D type "slow" reaction curves - shutoff power 10.000A - AC3.
CBr4 TAC3 REC
Maximum amps
Protection type (2)
2,9 A
D – 10.000A – AC3
3,1 A
D – 10.000A – AC3
3,5 A
D – 10.000A – AC3
4,8 A
D – 10.000A – AC3
34
print board)
Protection calibre
8A
8A
8A
8A