4.1.3 CPs Mode : setup, operating instructions and wiring diagrams
4.1.3.1 Setup CPs mode
The setup is made by means of the LCD screen and the 4 knobs SETUP,
the RC. To start the setup:
- Enter in the setup mode using the left knob on the diagram so that the SETUP LED ignites
- Press then the SETUP knob until the text 'SETUP' appears on the screen.
The idea is to select your choice with the
pressing 'ENTER'. The numbers are introduced digit by digit.
1
LANGUAGE
Choose your language (English, French, Dutch, German)
WORKING
Select CPs from CA, LS, CPs
2
MODE
CPs on
Select if you wish the constant pressure to operate on the exhaust or on the supply
3
SUPPLY
airflow.
Input of multiplier on the CPs assignment when contact between terminals +12V and
4
% on K3?
K3 in the CBr is closed or if knob III is activated on the RC
Type in ratio between exhaust (EXH) and supply (SUP) airflow to create over, under or
5
%EXH/SUP
even pressure.
INIT CPs
New initialization of the CPs constant pressure assignment? Y or N
6
REF?
INIT via
If Y is selected in 6 then select if you want to initialize the CPs reference automatically
7
AIRFLOW?
via the airflow or manually via the pressure value.
If INIT CPs via AIRFLOW (default): the DFE unit automatically determines the reference pressure
8
m³h INIT
Enter nominal airflow to determine assignment pressure CPs.
CPs INIT
Initializing of CPs busy.
xx,x V
After 1 minute the system will memorize the pressure measured by the sensor
9
corresponding to the nominal airflow.
xxxx m³h
Display of the actual airflow of the supply or exhaust fan (F1 or F3) and of the actual
xxxx Pa
sensor value.
ALARM
Possibility to reset the alarms Y or N
10
RESET?
END
The configuration of the system is finished.
11
SETUP
If INIT CPs via PRESSURE (see advanced setup): the user determines the reference pressure
CPs REF?
Enter the assignment pressure value.
8
xx,x V
ALARM
Possibility to reset the alarms Y or N
9
RESET?
END
The configuration of the system is finished
10
SETUP
Note that the CPs mode can be either active on the supply or the exhaust side of the unit (see 3, in table above):
CPs on SUPPLY air: The airflow delivered by the supply fan is automatically modulated to obtain a constant
pressure as measured by the pressure sensor in the duct. The exhaust airflow is equals to %EXT/PUL of the supply
airflow.
CPs on EXHAUST air: The airflow delivered by the exhaust fan is automatically modulated to obtain a constant
pressure as measured by the pressure sensor in the duct. The supply airflow is equals to 1/(%EXT/PUL) of the
exhaust airflow.
↑ ↓