5.5.3 Factory settings of parameters

0 00 Hot water set temperature for the operating mode "High Output"
01 Hot water set temperature for thermal disinfection
02 Heat retention function switch-on temperature
03 Heat retention switch-off temperature
04 Activation / deactivation of heat retention function
2 00 Start day thermal disinfection (Legionella protection)
01 Automatic thermal disinfection with switched on Hot water heat pump
02 Start time thermal disinfection
03 Automatic thermal disinfection in "Stand-by" mode
04 Holding time thermal disinfection temperature [0-01]
3 00 Automatic restart after a power failure
01 Access authorisation
02 Hot water set temperature >60°C
4 03 Simultaneous operation of the electrical Booster Heater (BOH) and
the heat pump.
6 00 Switching hysteresis of heat pump
01 Switch-off temperature difference heat pump
02 ECO timer (BOH)
03 Priority of operating mode "High Output"
04 Steps in the operating mode "Low Noise"
7 00 Behaviour in low tariff (HT/LT) - / Smart Grid (SG) mode
01 Switching hysteresis Booster Heater (BOH) when hot water set tem-
perature is above the maximum possible hot water temperature in
exclusively heat pump mode
02 Setting Emergency mode (use of BOH permitted or not)
C 00 Not used
E Display unit information
00 Software version
01 EEPROM version
02 Model ID
These parameters are only accessible in the "Advanced Mode" (see section 5.5.1).
Tab. 5-5 Overview parameter settings
DAIKIN EKHHP(3/5)00AA2V3
DAIKIN Hot water heat pump
008.1423444_02 – 09/2015
Parameter name
5
x
Operation, Parameters
Default factory settings
Value
Range
Increment
40
40 - 60
60
50 - 75
40
35 - 55
45
35 - 55
0
0 - 1
Fr
every day
0
0 - 1
23:00
0:00 - 23:00
0
0 - 1
10
5 - 60
1
0 - 1
3
2, 3
0
0 - 1
0
0 - 3
10
2 - 20
0
0 - 15
120
5 - 120
1
0 - 1
1
1 - 3
0
0 - 3
2
2 - 20
0
0 - 1
0
Information value, cannot be changed.
Information value, cannot be changed.
Information value, cannot be changed.
Installation and maintenance manual
Unit
1
°C
1
°C
1
°C
1
°C
1
0
1:00
h
1
1
Min.
1
1
1
1
1
K
1
K
1
Min.
1
1
1
1
°C
1
27