An ON temperature > 45°C makes sure that only
the electrical Booster Heater (BOH) is used and not
the heat pump. This increases the usage duration of
the refrigerant compressor.
In the operating modes "ECO" and "Automatic" the
hot water heating mode only starts when the
measured hot water temperature falls below 45°C.
– [6-01] Stop: Temperature difference that determines the OFF
temperature of the heat pump (T
T
Water temperature
T
Maximum water temperature of the heat pump at the
HP MAX
temperature sensor in the hot water storage tank (55°C)
T
OFF temperature of the heat pump
HP OFF
T
ON temperature of heat pump
HP ON
T
hot water temperature (as set on the controller)
U
Fig. 5-5
Illustration of the control system for hot water generation by
the heat pump
– [6-02] GCO (BOH): stipulates when the Booster Heater
(BOH) can be started after the heat pump has been switched
on. This setting is only effective if simultaneous operation of
the Booster Heaters (BOH) and the heat pump is permitted
([4-03] is not set to 0).
– [6-03] Priority of "High Output" operating mode: stipulates the
priority if the operating modes "Low Noise" and "High Output"
are active at the same time.
Operating
mode
[6-03]
Off
0
OFF
Normal
ON
High output
1
OFF
Normal
ON
High output High output High output High output
Tab. 5-2 Overview of operating modes "Low Noise" and "High
Output" with simultaneous activation
If [6-03] is set to "1", the operating mode "High Out-
put" has priority over the operating mode "Low
Noise".
– [6-04] Stages in the operating mode "Low Noise":
– 1 = Lowest noise reduction.
– 2 = Medium noise reduction.
– 3 = Highest noise reduction.
DAIKIN EKHHP(3/5)00AA2V3
DAIKIN Hot water heat pump
008.1423444_02 – 09/2015
).
HP OFF
Settings
Operating mode
[6-04] = 1 [6-04] = 2 [6-04] = 3
Low Noise 1 Low Noise 2 Low Noise 3
Normal
Low Noise 1 Low Noise 2
Low Noise 1 Low Noise 2 Low Noise 3
5
x
Operation, Parameters
[7-00] - Low tariff mains connection (HT/LT) / Smart
Grid connection (SG)
These parameters facilitate the configuration of the DAIKIN Hot
water heat pump with an existing low tariff mains connection and
Smart Grid connection.
As soon as the function is activated by the parameter [7-00] > 0,
the operation of the DAIKIN Hot water heat pump is changed, de-
pending on the switch position of the connected potential-free ex-
ternal switching contact.
The following setting options are available:
– [7-00]: Stipulation as to whether the heat pump is connected
to a low tariff mains connection / Smart Grid connection.
– 0 = Normal mains connection (default setting).
– 1 = Evaluation low tariff mains connection.
– 2 = Evaluation low tariff mains connection.
– 3 = Evaluation low tariff mains connection and Smart Grid
connection.
[7-00]
Assessment contact
HT / LT
0 (default)
—
Open
1
Closed
Open
2
Closed
Open
Closed
Open
3
Closed
Tab. 5-3 Configuration table parameter [7-00]
[7-01] Switch hysteresis Booster Heater (BOH)
If the hot water set temperature is set to a value which is above
the maximum hot water temperature achieved in exclusively heat
pump mode, the electrical Booster Heater (BOH) is switched in
for hot water generation (see fig. 5-6).
The following setting options are available:
– [7-01] Switching hysteresis Booster Heater (BOH) when hot
water set temperature is above the maximum possible hot
water temperature in exclusively heat pump mode.
Factory setting 2 K
Behaviour of heat
pump
SMART
GRID
—
Normal operating
mode
—
Normal mode
(low tariff)
—
Reduced mode
(high tariff)
—
Reduced mode
(high tariff)
—
Normal mode
(low tariff)
Open
Normal operating
mode
Open
Reduced mode,
expensive power
Closed
Switch-on recom-
mendation,
cheap power
Closed
Switch-on
command,
cheap power
Installation and maintenance manual