If the installation conditions require the hydraulic
connection to be directly upwards, the cover
hood can be cut out along the broken line.
Fig. 2-4
Creating the hood cut-out
Pay attention to the stipulated tightening torque
(see section 2.1).
– Design the lines as such that the sound attenuation cowl
can be applied without any problem following assembly.
WARNING!
There is a danger of scalding at hot water tem-
peratures over 60°C. This is possible, when
solar energy is used, with a connected external
heating device, when the Legionella protection
is activated or when the domestic hot water
target temperature is set higher than 60°C.
● Install scald protection (hot water mixer).
– Water shortage protection: The temperature monitoring
of the controller safely switches off the DAIKIN EKHHP in
the event of a water shortage. No additional water short-
age protection is needed in the construction. Neverthe-
less, regular checking of the fill level is necessary in order
to ensure function as intended.
– Avoid damages caused by deposits and corrosion:
Observe the requirements for the buffer water storage
(see section 1.5.6).
DAIKIN EKHHP(3/5)00AA2V3
DAIKIN Hot water heat pump
008.1423444_02 – 09/2015
2
x
Set-up and installation
Fig. 2-5
Hydraulic connection - legend see tab. 2-2
(Example EKHHP500AA2V3 with
auxiliary heater)
1
Cold water connection
2
Hot water distribution network
3
Feed
Solar or for other heat source*
4
Return
Solar or for other heat source*
6
Circulation*
7
Customer's side: Check valve, return valve
7a
Circulation brakes (2 in number) Recommended accessory
8a
Feed
Solar or for other heat source*
8b
Return
Solar or for other heat source*
9
Gas line (refrigerant)
10
Liquid line (refrigerant)
EKHHP
DAIKIN Heat pump indoor unit
EKSRPS4A
DAIKIN Solar regulation and pump unit*
FLG FlowGuard - Solar regulating valve with flow indicator*
ERWQ
DAIKIN Heat pump external unit
FLS FlowSensor - Solar flow and feed flow temperature
measurement*
P
Boiler circulation pump*
K
P
Circulation pump*
Z
SK
Solar panel field*
SV
Customer's side: Safety over-pressure valve
W
External heat generator*
EX
*
Optional
Tab. 2-2 Legend for fig. 2-5
● Carefully insulate pipe lines against heat loss and so as to
avoid the formation of condensation (insulation thickness at
least 20 mm).
Solar and optional
Installation and maintenance manual
11