INSTALLATION
GENERAL
The ue gas exhaust and hydraulic connections must be carried out by quali ed personnel who must issue installation conformity
documentation compliant with national standards.
The installer must provide the owner or person acting for him, according to the legislation in force, with the declaration of conformity,
supplied with:
1) the use and maintenance manual of the appliance and of the system components (such as for example, the smoke ducts, chimney, etc.);
2) photocopy or photograph of the chimney plaque;
3) system booklet (where applicable).
The installer must ask to be issued with a receipt stating that the documentation has been provided, and must keep it with a copy of the technical
documentation relating to the installation.
For installation in a condominium, prior approval from the condominium's administrator must be requested.
Where required, check the exhaust gas emissions after installation. Should a sampling point be installed, it must be airtight.
COMPATIBILITY
Do not install in rooms with a re hazard. It is also forbidden to install it in living areas with the following characteristics:
1. where there are liquid fuel appliances with continuous or discontinuous operation that draw the combustion air into the room in which they
are installed.
2. where there are type B gas appliances intended for heating, with or without domestic hot water production and in adjacent and communicating
rooms.
3. where the depression measured in situ between the external and internal environment is greater than 4 Pa.
N.B.: Watertight appliances can also be installed in the cases indicated in points 1, 2 and 3 of this paragraph.
INSTALLATIONS IN BATHROOMS, BEDROOMS AND STUDIO FLATS
Installation in bathrooms, bedrooms and studio ats is only allowed for sealed or closed hearth appliances with ducted combustion air taken
from the outside.
POSITIONING AND SAFETY DISTANCES
The support surfaces and/or points must have a suitable capacity to bear the overall weight
of the appliance, accessories and coverings. If the oor is made of a combustible material,
we recommend using a non-combustible material to protect the front part from any burnt
material which might fall during routine cleaning operations. The generator must be level
to function properly. The side walls, the rear walls and the oor support surface should be
made of non-combustible material.
MINIMUM DISTANCES
Installation next to ammable or heat-sensitive materials is permitted only if the special
safety distances speci ed on the label at the beginning of the manual (pag.2) are
observed. If the materials are not ammable, you must keep a side and rear distance of at
least 100 mm (without the inserts). For products equipped with rear spacers, wall-mounting
installation is permitted exclusively for the rear side.
PREPARATIONS FOR MAINTENANCE
To carry out extraordinary maintenance operations on the product, it may be necessary to move it away from the adjacent walls. This must be
done by a technician authorised to disconnect the combustion product evacuation ducts and then reconnect them. For heaters connected to the
hydraulic system, the connection between the system itself and the product must be made in such a way that, when an authorised technician is
about to carry out extraordinary maintenance operations, it is possible to move the heater at least 1 metre away from the adjacent walls.
INSTALLING INSERTS
When installing inserts, access must be prevented to the internal parts of the appliance and it must not be possible to access live parts during
extraction operations.
Any wiring, for example the power cable or room probe, must be positioned so as not to be damaged during movement of the insert and must
not come into contact with hot parts. If a cavity made of combustible material is installed, we recommend taking all the safety precautions
indicated by the installation standards.
VENTILATION AND AERATION OF INSTALLATION ROOMS
In case of non-airtight heater and/or installation, the ventilation must respect the minimum area indicated below (considering the highest value
among those provided):
Appliance categories
Pellet stoves
Boilers
Under any condition, including in the presence of extractor hoods and/or of controlled forced ventilation systems, the pressure di erence
between the generator installation rooms and the outside must always be equal to or less than 4 Pa.
42
Reference standard
net opening section with respect to the
UNI EN 14785
UNI EN 303-5
One must also bear in mind all laws and national,
regional, provincial and town council regulations in force
in the country in which the appliance has been installed,
as well as the instructions contained in this manual.
Percentage of the
appliance fumes outlet section
-
50%
ENGLISH
Air inlet
oor protection
Minimum net opening value of the
ventilation duct
80 cm²
100 cm²