The appropriately wrapped and protected cover is inside the packing:
- unpack it carefully, check the integrity of the part and install it after placement of the stove, as follows:
X - position the cover, respecting the position of the 4 vibration dampers (detail A) on the stove which allow its
centring.
Y - secure the cover in place, fixing the middle stop without forcing, as shown in the figure.
X
Y
2.3 Air inlet
The stove air inlet pipe or intake is located at the back and is round and 50 mm in diameter.
A quantity of air at least equal to that necessary for combustion must flow in the room where the stove is installed;
therefore the combustion air necessary to ensure correct operation of the stove must be drawn:
from the room, provided there is a wall air inlet near the stove, communicating with the outside and of minimum
►
area 100 cm² suitably protected externally by a grille;
or with direct connection to the outside with an appropriate pipe having a minimum internal diameter of 50 mm
►
and maximum length of 1.5 m, provided with antiwind protection at the end (down bend).
The air inflow can also be obtained from a room adjoining that of installation, provided the flow can occur freely
through permanent openings to the outside; the room must not be used as a garage, for storing combustible
materials or for activities with fire risk.
Vibration
DETAIL A
SCALE 1: 2
STOPS
DETAIL A
SCALE 1: 2
45
ELLISSE CAN 2011