Installation; Fuel Oil Gravity Feed Systems - Riello PRESS 45 N Manuel D'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3.

INSTALLATION

3.1

FUEL OIL GRAVITY FEED SYSTEMS

GRAVITY SYSTEM
For fuel oil with viscosity max. 7°E at 50°C.
SUCTION SYSTEM
For fuel oil with viscosity max. 7°E at 50°C.
RING SUPPLY
For heavy oil with viscosity up to 20°E / 50°C.
1 - Tank (properly heated for heavy oil)
2 - Filter (with resistance for oil > 7°E / 50°C)
3 - Burner (with kit for heavy oil)
4 - Couple of cocks (excluding the burner)
Notice: all the pipes have to be properly seized, sealed and heated (elec. resistance or hot steam or water) to let
the fuel flow.
Warning: before to put the burner in operation verify that no obstruction exists into the pipes, any obstruction
may damage the sealing of the pump.
5828
Priming pump:
loose the tap of the vacuometer plug (5,
fig. 1) and wait for the fuel flow.
H: Difference in the pipes height
L: Length of the suction pipe
D2629
Not advised, to be used only in
case of previously existing sys-
tem.
Never overcome the max. depres-
sion of 0.5 bar (38 cm Hg).
With higher values the fuel emanates
gas. The pipes shall be perfectly
D2630
sealead. When the tank is placed be-
low of the burner level, the return
pipe should reach the same level of
the suction pipe. In this case the foot
valve is not required.
5 - Forwarding pump
6 - Manometer
7 - Burner pump
8 - Pressure adjuster
3
GB
L meters
H
meters
ø 3/4"
ø 1"
0
5
10
0.5
8
15
1
11
20
1.5
14
25
2
17
30
L meters
H
meters
ø 1"
ø 1 1/4"
0
24
45
0.5
21
40
1
18
35
1.5
15
30
2
12
25
2.5
9
20
3
6
15
D2631

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

615 m34345233434524

Table des Matières