10.5. Automatisme du mode automatique (C65)
Applications Réseau/Groupe électrogène :
Loss of source 1?
yes
Failure Timer
Source 2 Available?
yes
no
ENGINE START
(GEN)
Source 2 Available?
yes
Availability Timer
Delayed
Transition? (DT)
yes
Go to CENTER-OFF
Dead band timer
yes
GO TO SOURCE 2
UTILITY-GENSET FLOWCHART
Contrôleur ATyS C55/C65 - 549866B - SOCOMEC
Pop-up alarm &
continue searching
GO TO CENTER-OFF
yes
Go to 0 active? (DT)
no
Alarm FAIL
no
START (GEN)
no
Source 1 and 2 are
lost?
In-phase timer is
yes
over?
no
Parameters in the window
yes
during Dwell time reset?
no
Inhibit/Bypass
yes
Inphase?
In-phase timer (dwell
time) start
yes
no
In-phase Transfer
enabled?
Retransfer
autorization
Engine Cool Down
Timer
GO TO SOURCE 1
Dead band Timer
Go to CENTER-OFF
yes
Delayed Transition?
no
(DT)
no
Manual retransfer
yes
active?
yes
Return Timer
yes
Source 1 is back?
FR
37