Operation in the menu
Walktest
Description
This function can be used to check the sys-
tem's detectors via a walktest. Any stored
messages from detector cover can be reset
using this function. The walktest is done with
the detection areas in a disarmed status.
Triggering of the detector is indicated by the
detector's red LED during a walktest.
Procedure
1. To call up the "WALKTEST" function from
the menu, see chapter "Calling up and end-
ing functions".
07: WALKTEST
2. Call up "WALKTEST".
By pressing the "ENTER" key, the first de-
tection area as well as its status with re-
spect to the walktest will be displayed.
ZO
01 =
OFF
ON
3. Call up additional detection areas for a
"WALKTEST".
By pressing the right
detection areas can be called up consecu-
tively. After the last detection area, detec-
tion area 1 reappears in the display.
ZO
02 =
OFF
ON
key, additional
- 20 -
4. Switch on "WALKTEST".
The "WALKTEST" of the detection area is
switched on by pressing the center
key.
AREA 02 = MNSTB
OFF
5. Conduct "WALKTEST".
Trigger movement alarm. A triggering of
the detector is indicated by the detector's
red LED.
6. Switch off "WALKTEST".
The "WALKTEST" for the detection area is
switched off by pressing the center
key.
ZO
02 =
OFF
ON
7. Return.
The "STOP" key causes a return by one
level. The menu will be displayed.
07: WALKTEST