Isolating A Detector In A Detector Zone - Bosch IUI-UEZ-BE1000s Manuel D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Operation in the menu

Isolating a detector in a detector zone

Description
This function can be used to isolate individual
detectors before the system is armed. Areas
with isolated detector zones can be entered if
the system is armed, without an alarm being
triggered. Not in compliance with VdS.
Procedure
1. To call up "ISOLATE ZONES" from the
menu, see chapter "Calling up and ending
functions".
06: ISOLATE ZONES
2. Call up detector zone.
By pressing the "ENTER" key, the first de-
tector zone that can be isolated and its
status (ON/OFF) will be displayed.
ZO
0001 = ON
v
3. Call up additional detector zones.
By scrolling with the
entry of the address using the number pad,
additional detectors zones that can be iso-
lated are displayed.
ZO
0002 = ON
v
4. Search for "Detector".
Press center
display of individual detectors.
ZO
0002 = ON
?
v
DETEC
keys or by direct
key 2 x to enable the
5. Call up detector.
By pressing the right
tector from the selected detector zone will
be displayed.
0002 – 01
v
6. Call up additional detectors.
By scrolling with the right
ticular detector from this detector zone can
be selected and displayed.
0002 – 13
v
7. Initiate isolation procedure.
Once the detector zone to be switched off
has been called up, the isolation procedure
is initiated by pressing the center
0002 – 13
ON
v
8. Isolate detector.
Press the right
tector. After isolation has been completed,
the new status of the detector (=OFF) will
be displayed.
0002 – 13
v
9.
Reset.
Press "STOP" key 2 x. The "STOP" key
causes a return by one level. The menu will
be displayed.
06: ISOLATE ZONES
- 19 -
key, the first de-
= ON
key, a par-
= ON
= ON
OFF
key to isolate the de-
= OFF
key.

Publicité

Table des Matières
loading

Table des Matières