Wiring - Lenze PROFIBUS-DP EMF2133IB Instructions De Montage

L−force communication
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4
Electrical installation

Wiring

Wiring
ƒ Only use cables which correspond to the listed specifications, see (^ 48).
ƒ Provide connection to the controllers by means of the bus connector. The bus system
will not be interrupted if the bus connector is removed from the controller.
ƒ Observe the notes and wiring regulations given in the documentation for the control
system.
ƒ Adapt baud rate to the bus cable length.
ƒ Check bus terminating resistors and activate them if necessary.
Specification of the transmission cable
Please follow the specifications of the PROFIBUS user organisation (PUO) for signal cables:
Bus cable specification
Specific resistance
Capacitance per unit length
Loop resistance
Core diameter
Core cross−section
Cores
Terminal data
Electrical connection
Possible connections
Tightening torque
Bare end
48
135 − 165
£
30 nF/km
W
< 110
> 0.64 mm
> 0.34 mm
Double twisted, insulated and shielded
Plug connector with screw connection
rigid: 1.5 mm
flexible:
without wire end ferrule
1.5 mm
with wire end ferrule, without plastic sleeve
1.5 mm
with wire end ferrule, with plastic sleeve
1.5 mm
0.5 ... 0.6 Nm (4.4 ... 5.3 lb−in)
6 mm
l
W
/km, (f = 3 − 20 MHz)
/km
2
2
(AWG 16)
2
(AWG 16)
2
(AWG 16)
2
(AWG 16)
EDKMF2133 DE/EN/FR 6.1