Lenze POWERLINK EMF2191IB Instructions De Montage
Lenze POWERLINK EMF2191IB Instructions De Montage

Lenze POWERLINK EMF2191IB Instructions De Montage

Module de communication

Publicité

Les langues disponibles

Les langues disponibles

Liens rapides

EDK2191DB
.Ma+
L−force Communication
POWERLINK
EMF2191IB
Kommunikationsmodul
Communication module
Module de communication
Montageanleitung
Mounting Instructions
Instructions de montage
l

Publicité

Table des Matières
loading

Sommaire des Matières pour Lenze POWERLINK EMF2191IB

  • Page 1 EDK2191DB L−force Communication .Ma+ Montageanleitung Mounting Instructions Instructions de montage POWERLINK EMF2191IB Kommunikationsmodul Communication module Module de communication...
  • Page 2 Lesen Sie zuerst diese Anleitung, bevor Sie mit den Arbeiten beginnen! Beachten Sie die enthaltenen Sicherheitshinweise. Please read these instructions before you start working! Follow the enclosed safety instructions. Veuillez lire attentivement cette documentation avant toute action ! Les consignes de sécurité doivent impérativement être respectées.
  • Page 3 2191EPL001B...
  • Page 4 Anzeigen Pos. Beschreibung LED−Statusanzeigen zur Diagnose Anschlüsse Pos. Beschreibung POWERLINK−Anschluss Ausführung: RJ45−Buchse nach IEC 60603−7 Anschluss zur externen Versorgung des Kommunikationsmoduls Ausführung: Steckerleiste mit Schraubanschluss, 2−polig Schalter Pos. Beschreibung Schalter zur Adressierung des Teilnehmers Linker Schalter: Einstellung mit Faktor 16 Rechter Schalter: Einstellung mit Faktor 1 Die Addition beider Produkte ergibt die Adresse (Node ID) des Teilnehmers Node ID = 254 (die Node ID wird von einem DHCP−Server bezogen)
  • Page 5: Table Des Matières

    Inhalt Über diese Dokumentation ..........Sicherheitshinweise .
  • Page 6: Über Diese Dokumentation

    Softwarestand Kommunikationsmodul EMF2191IB POWERLINK Zielgruppe Diese Dokumentation wendet sich an Personen, die das beschriebene Produkt nach Projekt- vorgabe installieren und in Betrieb nehmen. Tipp! Informationen und Hilfsmittel rund um die Lenze−Produkte finden Sie im Download−Bereich unter http://www.Lenze.com EDK2191DB DE/EN/FR 2.0...
  • Page 7: Sicherheitshinweise

    Sicherheitshinweise Sicherheitshinweise Stop! Elektrostatische Entladung Durch elektrostatische Entladung können elektronische Bauteile innerhalb des Kommunikationsmoduls beschädigt oder zerstört werden. Mögliche Folgen: Das Kommunikationsmodul ist defekt. ƒ Die Feldbus−Kommunikation ist nicht möglich oder fehlerhaft. ƒ Schutzmaßnahmen Befreien Sie sich vor dem Berühren des Moduls von elektrostatischen ƒ...
  • Page 8: Produktbeschreibung

    Produktbeschreibung Funktion Produktbeschreibung Funktion Das Kommunikationsmodul koppelt Lenze−Antriebsregler an das Kommunikationssystem Ethernet POWERLINK. Bestimmungsgemäße Verwendung Das Kommunikationsmodul ... ƒ ist ein Betriebsmittel zum Einsatz in industriellen Starkstromanlagen; ƒ nur in POWERLINK−Netzwerken einsetzen; ƒ ist einsetzbar in Verbindung mit folgenden Grundgeräten (Typenschildbezeichnungen): Gerätetyp...
  • Page 9: Lieferumfang

    Produktbeschreibung Lieferumfang Lieferumfang ƒ Kommunikationsmodul EMF2191IB (POWERLINK) ƒ Montageanleitung Identifikation Type Id.-No. Prod.-No. MAC-ID  E82AF000P0B201XX 2191EPL013  33.2191IB Gerätereihe Hardwarestand Softwarestand EDK2191DB DE/EN/FR 2.0...
  • Page 10: Technische Daten

    24 V DC (20,4 V − 0 % ... 28,8 V + 0 %) 140 mA − Bezugspotenzial für externe Spannungsversorgung Dokumentationen zu Lenze Gerätereihen 8200 vector, 9300 und ECS Hier finden Sie die Umgebungsbedingungen und Daten zur Elektromagnetischen Verträglichkeit (EMV), die auch für das Kommunikationsmodul gelten.
  • Page 11: Abmessungen

    Technische Daten Abmessungen Abmessungen 2191EPL001B alle Maße in mm EDK2191DB DE/EN/FR 2.0...
  • Page 12: Mechanische Installation

    Mechanische Installation Mechanische Installation 2102LEC014 Abb. 1 Kommunikationsmodul aufstecken ƒ Stecken Sie das Kommunikationsmodul auf das Grundgerät (hier: 8200 vector). ƒ Schrauben Sie das Kommunikationsmodul mit der Befestigungsschraube auf dem Grundgerät fest, um eine gute PE−Verbindung sicher zu stellen. Hinweis! Zur internen Versorgung des Kommunikationsmoduls durch den Frequenzumrichter 8200 vector muss der Jumper in der Schnittstellenöffnung (siehe Abb.
  • Page 13: Elektrische Installation

    Elektrische Installation EMV−gerechte Verdrahtung Elektrische Installation EMV−gerechte Verdrahtung Für eine EMV−gerechte Verdrahtung beachten Sie folgende Punkte: Hinweis! Steuer−/Datenleitungen getrennt von Motorleitungen verlegen. ƒ Legen Sie die Schirme der Steuer−/Datenleitungen bei digitalen Signalen ƒ beidseitig auf. Zur Vermeidung von Potenzialdifferenzen zwischen den ƒ...
  • Page 14: Powerlink−Anschluss

    Elektrische Installation POWERLINK−Anschluss POWERLINK−Anschluss Zum Anschluss des Kommunikationsmoduls an den Feldbus eignet sich ein handelsübli- ches Standard−Ethernet−Patchkabel (siehe "Spezifikation des Ethernet−Kabels" (^ 15)). Hinweis! Um Beschädigungen der RJ45−Buchse zu vermeiden, den Stecker des Ethernet−Kabels gerade (im rechten Winkel) in die Buchse stecken bzw. aus der Buchse ziehen.
  • Page 15 Elektrische Installation POWERLINK−Anschluss Spezifikation des Ethernet−Kabels Hinweis! Verwenden Sie ausschließlich Kabel, die den aufgeführten Spezifikationen entsprechen. Spezifikation des Ethernet−Kabels Ethernet−Standard Standard Ethernet (nach IEEE 802.3), 100Base−TX (Fast Ethernet) Kabeltyp S/FTP (Screened Foiled Twisted Pair), ISO/IEC 11801 oder EN 50173, CAT 5e Dämpfung 23.2 dB (bei 100 MHz und je 100 m) Nebensprechdämpfung...
  • Page 16: Spannungsversorgung

    Elektrische Installation Spannungsversorgung Spannungsversorgung Interne Spannungsversorgung Hinweis! Die Vorgabe der internen Spannungsversorgung ist bei Grundgeräten mit erweiterter AIF−Schnittstellenöffnung (z. B. Frontseite 8200 vector) gegeben. Die in der Grafik grau hervorgehobene Fläche kennzeichnet die Jumper−Position. Im Auslieferungszustand des Grundgerätes werden diese nicht intern ƒ...
  • Page 17 Elektrische Installation Spannungsversorgung Externe Spannungsversorgung Hinweis! Verwenden Sie bei externer Spannungsversorgung und bei größeren Entfernungen zwischen den Schaltschränken in jedem Schaltschrank immer ein separates und nach EN 61800−5−1 sicher getrenntes Netzteil (SELV/PELV). Die externe Spannungsversorgung des Kommunikationsmoduls ... ƒ ist notwendig, wenn beim Ausfall der Versorgung des Grundgerätes die Kommunikation über den Feldbus bestehen bleiben soll.
  • Page 18: Inbetriebnahme

    Inbetriebnahme Vor dem ersten Einschalten Inbetriebnahme Vor dem ersten Einschalten Stop! Bevor Sie das Grundgerät mit dem Kommunikationsmodul erstmalig einschalten, überprüfen Sie die gesamte Verdrahtung auf Vollständigkeit, Kurzschluss und Erdschluss. Kommunikationshandbuch EMF2191IB (POWERLINK) Hier finden Sie ausführliche Informationen zur Inbetriebnahme des Kommunikationsmoduls.
  • Page 19: Teilnehmeradresse Einstellen

    Die Knotenadressen bei mehreren vernetzten Antriebsreglern müssen sich ƒ voneinander unterscheiden. Die Lenze−Einstellung für die Knotenadresse (Node ID) hat den Wert ’4’: – linker Schalter in Stellung ’0’ – rechter Schalter in Stellung ’4’ Um geänderte Einstellungen zu aktivieren, schalten Sie die ƒ...
  • Page 20: Diagnose

    Diagnose Diagnose Zur Störungsdiagnose stehen für das Kommunikationsmodul die auf der Frontseite plat- zierten LEDs zur Verfügung. Pos. Farbe Zustand Beschreibung grün Das Kommunikationsmodul ist mit Spannung versorgt, hat aber keine Verbindung zum Grundgerät (Grundgerät ist ausgeschaltet, in der Initialisierungsphase oder nicht vorhanden). Das Kommunikationsmodul ist mit Spannung versorgt und hat eine Verbindung zum Grundgerät.
  • Page 21 Diagnose EDK2191DB DE/EN/FR 2.0...
  • Page 22 Displays Pos. Description LED status displays for diagnostics Connections Pos. Description POWERLINK connection Version: RJ45 socket according to IEC 60603−7 Connection to external supply of the communication module Version: Connector with screw connection, 2−pole Switch Pos. Description Switches for addressing the nodes Left switch: Setting with factor 16 Right switch: Setting with factor 1 The addition of both products results in the node address (node ID)
  • Page 23 Contents About this documentation ..........Safety instructions .
  • Page 24: About This Documentation

    ƒ information on mechanical and electrical installation of the communication module; ƒ Safety instructions that must be observed; ƒ Information on versions of the Lenze standard devices to be used; ƒ technical data of the communication module; ƒ descriptions of the LED status displays for diagnostics.
  • Page 25: Safety Instructions

    Safety instructions Safety instructions Stop! Electrostatic discharge Electronic components of the communication module can be damaged or destroyed through electrostatic discharge. Possible consequences: The communication module is damaged. ƒ Fieldbus communication is not possible or faulty. ƒ Protective measures Discharge electrostatic charges before touching the module. ƒ...
  • Page 26: Product Description

    Product description Function Product description Function The communication module connects the Lenze inverter to the Ethernet POWERLINK communication system. Application as directed The communication module ... ƒ is a device intended for use in industrial power systems; ƒ can only be used in POWERLINK networks;...
  • Page 27: Scope Of Supply

    Product description Scope of supply Scope of supply ƒ Communication module EMF2191IB (POWERLINK) ƒ Mounting Instructions Identification Type Id.-No. Prod.-No. MAC-ID  E82AF000P0B201XX 2191EPL013  33.2191IB Device series Hardware version Software version EDK2191DB DE/EN/FR 2.0...
  • Page 28: Technical Data

    24 V DC (20.4 V − 0 % ... 28.8 V + 0 %) 140 mA − Reference potential for external voltage supply Documentation for Lenze series of devices 8200 vector, 9300 and ECS Here you can find the ambient conditions and the electromagnetic compatibility (EMC) specifications applying to the communication module.
  • Page 29: Dimensions

    Technical data Dimensions Dimensions 2191EPL001B All dimensions in mm EDK2191DB DE/EN/FR 2.0...
  • Page 30: Mechanical Installation

    Mechanical installation Mechanical installation 2102LEC014 Fig. 1 Attaching the communication module ƒ Plug the communication module onto the standard device (here: 8200 vector). ƒ Tighten the communication module to the standard device using the fixing screw in order to ensure a good PE connection. Note! For the internal supply of the communication module by the 8200 vector frequency inverter the jumper has to be adjusted within the interface opening...
  • Page 31: Electrical Installation

    Electrical installation Wiring according to EMC Electrical installation Wiring according to EMC For wiring according to EMC requirements observe the following points: Note! Separate control cables/data lines from motor cables. ƒ Connect the shields of control cables/data lines at both ends in the case of ƒ...
  • Page 32: Powerlink Connection

    Electrical installation POWERLINK connection POWERLINK connection You can use a standard Ethernet patch cable for connecting the communication module to the fieldbus (see "Ethernet cable specifications" (^ 33)). Note! Plug/remove the Ethernet cable plug in a straight manner (at right angles) into/from the socket to make sure that the RJ45 socket will not be damaged.
  • Page 33 Electrical installation POWERLINK connection Ethernet cable specifications Note! Only use cables complying with the below specifications. Ethernet cable specifications Ethernet standard Standard Ethernet (according to IEEE 802.3), 100base TX (fast Ethernet) Cable type S/FTP (Screened Foiled Twisted Pair), ISO/IEC 11801 or EN 50173, CAT 5e Damping 23.2 dB (at 100 MHz and per 100 m)
  • Page 34: Voltage Supply

    For internal voltage supply place the jumper on the position indicated ƒ below. In the case of all other device series (9300, ECS), voltage is always supplied from the standard device. Lenze setting Internal voltage supply (Only external voltage supply possible.) EDK2191DB DE/EN/FR 2.0...
  • Page 35 Electrical installation Voltage supply External voltage supply Note! In the case of an external voltage supply and for greater distances between the control cabinets, always use a separate power supply unit (SELV/PELV) that is safely separated in accordance with EN 61800−5−1 in each control cabinet. The external voltage supply of the communication module ...
  • Page 36: Commissioning

    Commissioning Before switching on Commissioning Before switching on Stop! Before switching on the standard device with the communication module for the first time, check the entire wiring for completeness, short circuit and earth fault. Communication manual EMF2191IB (POWERLINK) Here you will find detailed information on how to commission the communication module.
  • Page 37: Setting The Node Address

    Note! Use different node addresses for several networked inverters. ƒ The Lenze setting for the node address (node ID) has the value ’4’: – link switch in position ’0’ – right switch in position ’4’ Switch the voltage supply of the inverter/communication module off and ƒ...
  • Page 38: Diagnostics

    Diagnostics Diagnostics The LEDs on the front are provided to the communication module for the purpose of fault diagnostics. Pos. Colour Condition Description green The communication module is supplied with voltage, but has no connection to the basic device (basic device is either switched off, in the initialisation phase, or not available).
  • Page 39 Diagnostics EDK2191DB DE/EN/FR 2.0...
  • Page 40: Commutateur

    Affichages Pos. Description Affichages d’état (LED) pour diagnostic Raccordements Pos. Description Raccordement POWERLINK Version : prise RJ45 suivant CEI 60603−7 Raccordement pour l’alimentation externe du module de communication Version : bornier à vis, 2 bornes Commutateur Pos. Description Commutateurs pour adressage du participant au bus Commutateur de gauche : réglage avec facteur 16 Commutateur de droite : réglage avec facteur 1 La somme des deux réglages donne l’adresse (identificateur nœud) du participant au bus.
  • Page 41 Sommaire Présentation du document ..........Consignes de sécurité...
  • Page 42: Présentation Du Document

    ƒ des consignes de sécurité qui doivent impérativement être respectées, ƒ les indications des versions des appareils de base Lenze à utiliser, ƒ les spécifications techniques du module de communication, ƒ les descriptions des affichages d’état (LED) pour diagnostic.
  • Page 43: Consignes De Sécurité

    Consignes de sécurité Consignes de sécurité Stop ! Décharge électrostatique Des composants électroniques à l’intérieur du module de communication peuvent être endommagés ou détruits par des décharges électrostatiques. Risques encourus : Le module de communication est endommagé. ƒ La communication par bus de terrain est impossible ou erronée. ƒ...
  • Page 44: Description Du Produit

    Description du produit Fonction Description du produit Fonction Le module de communication relie le variateur de vitesse Lenze au système Ethernet POWERLINK. Utilisation conforme à la fonction Le module de communication... ƒ est un équipement à utiliser dans des installations industrielles à courant fort ;...
  • Page 45: Equipement Livré

    Description du produit Equipement livré Equipement livré ƒ Module de communication EMF2191IB (POWERLINK) ƒ Instructions de montage Identification Type Id.-No. Prod.-No. MAC-ID  E82AF000P0B201XX 2191EPL013  33.2191IB Série d’appareils Version matérielle Version logicielle EDK2191DB DE/EN/FR 2.0...
  • Page 46: Spécifications Techniques

    24 V CC (20.4 V − 0 % ... 28.8 V + 0 %) 140 mA − Potentiel de référence pour l’alimentation externe Documentations relatives aux séries d’appareils Lenze 8200 vector, 9300 et Ces documentations décrivent les conditions ambiantes et les données de compatibilité électromagnétique (CEM), qui sont également valables pour le module de communication.
  • Page 47: Encombrements

    Spécifications techniques Encombrements Encombrements 2191EPL001B Toutes les cotes en mm EDK2191DB DE/EN/FR 2.0...
  • Page 48: Installation Mécanique

    Installation mécanique Installation mécanique 2102LEC014 Fig. 1 Brancher le module de communication ƒ Enficher le module de communication dans l’appareil de base (ici : 8200 vector). ƒ Visser le module de communication sur l’appareil de base à l’aide de la vis de fixation pour assurer une bonne liaison avec la terre.
  • Page 49: Installation Électrique

    Installation électrique Câblage conforme CEM Installation électrique Câblage conforme CEM Pour s’assurer que le câblage est conforme aux exigences à respecter en matière de CEM, vérifier les points suivants : Remarque importante ! Séparer physiquement les câbles de commande/de données des câbles ƒ...
  • Page 50: Raccordement Powerlink

    Installation électrique Raccordement POWERLINK Raccordement POWERLINK Le module de communication peut être raccordé au bus de terrain à l’aide d’un câble droit Ethernet standard en vente dans le commerce (voir "Spécifications du câble Ethernet" (^ 51)). Remarque importante ! Enficher ou retirer le connecteur du câble Ethernet verticalement (angle droit) afin d’éviter tout endommagement de la prise RJ45.
  • Page 51 Installation électrique Raccordement POWERLINK Spécifications du câble Ethernet Remarque importante ! Utiliser exclusivement des câbles conformes aux spécifications indiquées. Spécifications du câble Ethernet Standard Ethernet Ethernet standard (selon IEEE 802.3), 100Base−TX (Fast Ethernet) Type de câble S/FTP (Screened Foiled Twisted Pair), ISO/CEI 11801 ou EN 50173, CAT 5e Atténuation 23.2 dB (pour 100 MHz et par segment de 100 m)
  • Page 52: Alimentation

    Installation électrique Alimentation Alimentation Alimentation interne Remarque importante ! Les appareils de base dotés d’une interface AIF étendue (face avant du 8200 vector par exemple) offrent la possibilité d’une alimentation interne. Sur l’illustration, la partie grisée désigne la position du cavalier. L’état à...
  • Page 53 Installation électrique Alimentation Alimentation externe Remarque importante ! En cas d’alimentation externe et d’écarts importants entre les armoires électriques, toujours utiliser un bloc d’alimentation avec coupure de sécurité (SELV/PELV) distinct et conforme à la norme EN 61800−5−1 pour chaque armoire électrique. L’alimentation externe du module de communication ...
  • Page 54: Mise En Service

    Mise en service Avant la première mise sous tension Mise en service Avant la première mise sous tension Stop ! Avant la première mise sous tension de l’appareil de base avec le module de communication, vérifier si le câblage a été correctement réalisé dans son intégralité...
  • Page 55: Réglage De L'adresse Des Participants

    Les adresses de nœud des différents variateurs reliés doivent être ƒ univoques. Par le réglage Lenze, l’adresse du nœud (identificateur nœud) est ’4 ’: – commutateur de gauche en position ’0’ – commutateur de droite en position ’4’ Pour activer un réglage modifié, procéder à une coupure et remise sous ƒ...
  • Page 56: Diagnostic

    Diagnostic Diagnostic Les LED situées sur la face avant permettent d’effectuer le diagnostic des défauts du module de communication. Pos. Couleur Etat Description Le module de communication est sous tension, mais la liaison verte avec l’appareil de base n’est pas établie (l’appareil de base est hors tension, en cours d’initialisation ou aucun appareil de base n’est détecté).
  • Page 57 Diagnostic EDK2191DB DE/EN/FR 2.0...
  • Page 58 © 10/2013 Lenze Automation GmbH Service Lenze Service GmbH Hans−Lenze−Str. 1 Breslauer Straße 3 D−31855 Aerzen D−32699 Extertal Germany Germany +49 (0)51 54 / 82−0 00 80 00 / 24 4 68 77 (24 h helpline) Ê Ê +49 (0)51 54 / 82 − 28 00 +49 (0)51 54 / 82−11 12...

Table des Matières