5

Electrical installation

Wiring according to EMC

5
Electrical installation
Wiring according to EMC
Please observe the following for wiring according to EMC guidelines:
)
Note!
Separate control cables from motor cables.
ƒ
Lead the shields as far as possible to the terminals (unshielded core length
ƒ
< 40 mm).
Connect control and data cable shields as follows:
ƒ
– Analog signal cable shields must be connected with one end at the
inverter.
– Digital signal cable shields must be connected with both ends.
More information about wiring according to EMC guidelines can be
ƒ
obtained from the corresponding documentation for the standard device.
How to connect the shield

1. Prepare cable.
2. Insert cable tie into shield sheet.
3. Insert cable and tighten cable tie. Shield and shield sheet must be tightly connected.