Wiring according to EMC
5
Electrical installation
Wiring according to EMC
Please observe the following for wiring according to EMC guidelines:
)
Note!
Separate control cables from motor cables.
ƒ
Lead the shields as far as possible to the terminals (unshielded core length
ƒ
< 40 mm).
Connect control and data cable shields as follows:
ƒ
– Analog signal cable shields must be connected with one end at the
inverter.
– Digital signal cable shields must be connected with both ends.
More information about wiring according to EMC guidelines can be
ƒ
obtained from the corresponding documentation for the standard device.
How to connect the shield
1. Prepare cable.
2. Insert cable tie into shield sheet.
3. Insert cable and tighten cable tie. Shield and shield sheet must be tightly connected.