ALARMS SHOWN ON THE CONTROL PANEL OF THE EXTERNAL UNIT
The control panel of the external unit allows access to the alarms that should activate during the operation of the heat pump.
The operating light ref. 2 fig. 23 flashes in the event of a fault.
To do so, keep the pushbuttons
The code of the last alarm will appear to the right hand side of the display while on the left side the alarm code will be shown.
With the arrows
or
To cancel the alarms press the
To return to the normal operating position press the
Symptoms and inspection points.
Alarms
Meaning
displayed
P03
Anomalous
temperature
Reflow temperature > or =
to the limit temperature
P05
Phase absence detection
(CT
disconnected
defect
in
supply)
P15
Insufficient cooling power
detected
P19
Blocked 4-way valve.
This warning appears after
the compressor has been
operating for 5 minutes.
P20
High pressure protection
activated due to an excess
of the C2 temperature in
cold mode.
P22
External fan motor defect,
circuit protection
Inverter
activated
blocked on the external fan
motor
and
pressed simultaneously for 5 seconds.
to the right of the box, scroll the codes of the other 3 previous alarms.
key.
key.
Condition for the
alarm signalling
reflow
The device stops the
moment
that
temperature
111°C
The value of the intensity
or
of current sent by MDC to
the
power
the external board is low.
Lack of electric power for
3 or more minutes
1 minute of continuous
operation in the following
conditions:
- T° reflow of 95°C or
greater
- Opening of the electronic
pressure regulator at 480
Pas
- Value of the intensity of
current of MDC equal to
1.7 A (three-phase) or 1.0
A (single-phase) or less
T° exceeds 64°C and no
longer drops below 55°C
[min (E1, E2)] ≤ 10°C
T°
of
the
exchanger increases even
though it is in cold mode
[E2 ≥ 40°C]
The temperature exceeds
65°C and no longer drops
below 55°C or less
> 30 s of continuous
operation: the alarm is
displayed when the first
case occurs
< 30 s of continuous
operation: the Inverter is
stopped
The Inverter stops after the
intervention of the alarm
or
GB
Alarm interruption
conditions
Interruption during restart
the
exceeds
Interruption during restart
Interruption during restart
Interruption during restart
internal
Interruption during restart
Interruption during restart
4.2
4.2.1
Check and
connections
1. Check the refrigeration
cycle (for any leaks)
2. Defect of the pressure
regulator
3. Check
the
reflow
probe
1. Check the presence
and
sequence
of
phases R, S and T
2. Check the Inverter
board
3. Check
the
main
external board
Check the refrigeration
cycle (for any leaks)
1. Check the 4-way valve
2. Check the electrical
power supply of the 4-
way valve
3. Check the external
electronic board
1. Thermodynamic cycle
overheating
2. Check
the
C2
temperature probe
1. Positioning
defect
detected
2. Protection
circuit
against overloading
due to overcurrent of
the external fan motor
activated:
- check the external
electronic board
- see
the
checking
method of the external
fan
SHERPA
4
55