The measured variable I or U AC is isolated from the elec-
tronics by the transformer W, and is rectified and smoothed
in the rectifier unit G following. The output amplifier V, re-
ceiving its power supply from the measuring input, converts
this quantity into a load-independent DC output signal.
W
I~
U~
Fig. 3. Block diagram for a function unit.

4. Technical data

General
Measured quantity:
AC current or AC voltage sinusoi-
dal
Arithmetical mean measured, cali-
bration to rms with sinus form
Measuring principle:
Rectifier
Measuring input E
Nominal frequency f
: 50 or 60 Hz
N
Nominal input current I
N
(measuring range
end value) :
1, 1.2, 5 or 6 A
Nominal input voltage U
N
(measuring range
end value):
100/√3, 110/√3, 120/√3, 100, 110,
116.66, 120, 125, 133.33, 150, 250,
400 or 500 V
Own consumption at nominal frequency 50 Hz:
Full output value
per current input
I
[mA]
AN
1
5
10
20
16
G
V
per voltage input
[VA]
[VA]
0.8
0.8
1.8
1.2
2.2
1.5
2.5
1.8
Overload capacity:
Measured
Number of
quantity
applications
I
, U
N
N
1.5 x I
continuously
N
2
x I
N
10
x I
N
40
x I
N
A
1.5 x U
continuously
N
2
x U
N
4
x U
N
Measuring output A
Output variables:
Standard ranges of I
Standard ranges of U
Current limit under
overload:
Voltage limit under
R
= ∞ :
ext
Output current ripple:
Response time:
Accuracy data (according to DIN/IEC 688-1)
Reference value:
Basic accuracy:
Reference conditions
Ambient temperature
Input
Frequency
Distortion factor
External resistance:
Influence effects (maxima)
(included in basic error)
Linearity error
Frequency f
± 2%
N
Dependence on external
resistance ∆ R
ext
Duration of
Intervals between
one
two successive
application
–––
10
10 s
5
3 s
1
1 s
–––
10
10 s
1
2 s
Load-independent DC current I
or
DC voltage output U
imposed)
: 0...1, 0...5, 0...10 or 0...20 mA
A
Burden voltage 15 V
External resistance
R
max. [kΩ] =
ext
I
I
= Full output value
AN
: 0...10 V
A
External resistance ≥ 200 kΩ/V
≤ 1.5 x I
for current output
AN
approx. 30 mA for voltage output
< 24 V
≤ 0.5% p.p.
< 300 ms
Input end value
Class 0.5
23 °C, ± 5 K
0 to 100%
at current measurement
20 to 100%
at voltage measurement
f
± 2%
N
< 0.5%
0 – R
max.
ext
± 0.3%
± 0.3%
max. ± 0.1%
applications
–––
10 s
5 min.
–––
–––
10 s
–––
A
(not super-
A
15 V
[mA]
AN