Preparation • Never install the pump outside of the building.
Rotating the motor
head
Installation and operating instructions Wilo-Para
• Choose an installation point that is as easily accessible
as possible.
• Observe the pump's permitted installation
position (Fig. 2) and rotate the motor head (2+5) if
necessary.
CAUTION!
An incorrect installation position may damage the
pump.
• Select the installation point according to the permit-
ted installation position (Fig. 2).
• The motor must always be installed horizontally.
• The electrical connection must never face upwards.
• Install shut-off devices upstream and downstream of
the pump to facilitate pump replacement.
CAUTION!
Leaking water may damage the control module.
• Align the upper shut-off device such that leaking
water cannot drip onto the control module (5).
• Align the upper shut-off device laterally.
• When installing in the feed of open systems, the
safety supply must branch off upstream of the pump
(EN 12828).
• Complete all welding and brazing work.
• Flush the pipe system.
Rotate the motor head (2+5) before installing and con-
necting the pump.
• If necessary, remove the thermal insulation shell.
WARNING!
Risk of fatal injury from magnetic field!
Risk of fatal injury for people with medical implants due
to permanent magnets installed in the pump.
• Never remove the rotor.