Table 16. Configuration Mode LEDs and Options
Bar Graph Indicators
Option
230V Nominal Input
Voltage
g
220V Nominal Input
Voltage
g
240V Nominal Input
Voltage
g
Site Wiring Fault
Alarm
AC Input Failure
Alarm
Alarm
®
EATON Powerware
LED Status
Explanation
On (default)
Selecting this option changes the nominal input voltage
to 230V.
Flashing
230V is disabled; one of the other input voltage options is
selected.
On
Selecting this option changes the nominal input voltage
to 220V.
Flashing
220V is disabled; one of the other input voltage options is
(default)
selected.
On
Selecting this option changes the nominal input voltage
to 240V.
Flashing
240V is disabled; one of the other input voltage options is
(default)
selected.
On (default)
Alarm sounds when the polarity of the outlet is reversed
or the ground connection is missing; have a qualified
electrician repair the outlet wiring.
Flashing*
Alarm DOES NOT sound when the polarity of the outlet is
reversed or the ground connection is missing.
* Site Wiring Fault is not available for 230V models;
Flashing is the default.
On (default)
Alarm sounds when there is an AC input failure.
Flashing
Alarm DOES NOT sound when there is an AC input
failure.
9125 (9910-P30) UPS Installation Guide for IBM
®