To hardwire the UPS:
Powerware
5140 Installation Guide for IBM Applications
®
1. Switch off utility power at the distribution point where the UPS
will be connected. Be absolutely sure there is no power.
2. Remove the terminal block cover and either the input wiring
knockout or removeable plate (see Figure 10). Retain the
terminal block cover.
Input Wiring Access
with Removable Plate
3. Pull the input wires through the conduit, leaving approximately
2 ft (0.5m) of exposed wire. Attach a flexible metal fitting to the
end of the conduit.
4. Insert the conduit through the input wiring entry and attach
the conduit fitting to the panel. Strip 0.5
insulation from the end of each incoming wire.
05146790 A Uncontrolled Copy
S
Terminal Block Cover
Figure 10. Wiring Access
I
Installation
Input Wiring Access
Knockout
(1.5 cm) of
9