UK | 14 RLS 45 K – commissioning software
Basic settings
Parameter
Luminosity
LED indicator
Luminosity
LED standby
Time LED auto.
Standby
Ventilation
Parameter
Filter service life
unit filter
Filter change unit
filter: Acknowledge-
ment
Duration ventilation
level level 5 (intermit-
tent ventilation)
60
Set value
2, 3, 4, 5
0, 1, 2
0 ... 3 ... 6 minutes
Set value
1 ... 6 ... 8 months
changed,
not changed
5 ... 30 ... 90 minutes
Parameter
Duration night time
level 0 (sleep mode)
Sensors
Parameter
Relative humidity
min. limit value
(HPV)
Relative humidity
max. limit value (IV)
CO
limit value
2
min.
CO
limit value
2
max.
VOC limit value
min.
VOC limit value
max.
PPB 30 K
relative humidity
min. limit value
(HPV)
PPB 30 K
relative humidity
max. limit value (IV)
Set value
15 ... 60 ... 120 mi-
nutes
Set value
35 ... 35 ... 50 % rel.
hum.
55 ... 60 ... 70 % rel.
hum.
500 ... 800 ... 900 ppm
1000 ... 1200 ... 1500
ppm
500 ... 800 ... 900 ppm
1000 ... 1200 ... 1500
ppm
35 ... 40 ... 45 % rel.
hum.
50 ... 70 ... 85 % rel.
hum.